Data Sheet
108-20090
Rev. C1 
Page 4 of 14
LOC I
FTEC174 rev. 1 July 99 
3.0  TEST REQUIREMENTS AND PROCEDURES SUMMARY: 
FEATURES  TEST CONDITIONS  LIMITS 
3.1 
Voltage Drop 
(mated connectors) 
Between  two  points  on  wires  at 
1cm from the housing edges. 
Test currents: 
 6A for 0,5sqmm wire 
11A for 1,0sqmm wire 
14A for 1,5sqmm wire 
≤ 3 mV/A on new contacts. 
The voltage drop of wire must 
be subtracted 
3.2 
Contact resistance 
(mated contacts) 
Between the ends of crimps. 
Test current: 10mA 
≤ 3 mΩ on new contacts. 
3.3 
Insulation Resistance 
(mated connectors) 
Between adjacent contacts apply 
500 Vd.c. for 1 min. 
≥ 200 MΩ 
(new contacts) 
3.4 
Dielectric withstanding 
voltage 
Between adjacent contacts apply 
1500Va.c. for 1 min. 
No breakdown or flashes 
3.5 
Connector mating force 
Mate connectors with their 
contacts loaded at a speed of 
25÷100mm/min 
1 pos. conn.: 
≤ 80N 
2÷6 pos. conn.: 
≤ 120N 
3.6 
Connector unmating 
force 
Unmate connectors with their 
contacts loaded at a speed of 
25÷100mm/min: 
a)  Without operate the locking 
lance 
b)  Operating the locking lance 
a) All positions: 
 ≥ 145N 
b) 1 pos. conn.: 
 ≤ 80N 
 2÷6 pos. conn.: 
 ≤ 120N 