Special Safety Instructions: 
Standard Specific Safety Instructions: 
Whilst all individual outputs are classed as SELV outputs in accordance with the standard 
IEC/EN/UL/CSA60950-1 (<60Vdc or 42.4V peak), seriesed combinations of these outputs may exceed these 
values and become hazardous output voltages. 
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the 
equipment may be impaired. 
Environmental Specifications:  
Description  Operation  Storage 
Use  Indoor  - 
0°C - +70°C (derating at 2.5%/°C from 50°C) 
Temperature 
(For ZPSA40/60 -3,-5,-9) 
0°C - +70°C derating at 2.5%/°C from 40°C) 
-20°C - +85°C 
Humidity  10 - 95% RH, non-condensing  10 - 95% RH, non-
condensing 
Altitude  2000M  2000M 
Orientation  See Fig 1  ALL 
Material Group  IIIb 
Pollution Degree  2 
IP Protection Class  IPX0 
Level of Insulation: 
Dielectric Strength testing is carried out as follows: 
Primary mains to earth: 1.5kVAC 
Primary mains circuits to secondary: 3kVAC, 4142VDC 
Output to earth isolation 500VDC 
.Safety Approvals: 
UL/cUL60950-1 (2
nd
 Edition) 
IEC / EN60950-1(2
nd
 Edition) 
CE marking when applied to any ZPSA100-xx product indicates compliance with the Low Voltage Directive 
(2006/95/EC) in that it complies with EN60950-1 (2
nd
 Edition). 
Fusing:  Internal fuses (F1): Single fuse in the L line, T2AL, 250V, 
Input Connection 
ACN – Neutral  ACL – Live 
Input connector mates with Molex housing 09-50-3031 and Molex 2878 series crimp terminal 
ZPSA100 –xx 