Datasheet

ZMS100 Series
,QGXVWULDO 7HVW
ZMS100 Series
1
www.emea.tdk-lambda.com/zms
&RPP
%URDGFDVW
0HGLFDO
/('
Features Benets
• Long e-cap lifetime • Better eld reliability and service life
• Compact 2 x 4 inch footprint • Space saving in end equipment
• Medical approval with 2 x MoPP isolation • Suitable for B and BF type medical equipment
• Suitable for Class I and Class II installations • Flexible utilisation
• Ceramic start-up cap • Eradicates start-up cap dry out problems
80W Convection, 100W
Forced-Air Cooled
Single Output Power Supplies
Specication
Model ZMS100
AC Input Voltage range (2) (4) - 85 - 264VAC (47-63Hz) 120 - 350VDC
Input Fusing Line and neutral
Input Current (Typ) (230V/115Vac) A 1.0 / 2.0
Inrush Current - cold start A <40 (max at 264Vac input)
Harmonic Compliance - Compliant to EN/IEC61000-3-2 class A
Temperature Coefcient - <0.02% / °C
Typical Hold Up Time at 80W load,115/230Vac
ms 22 / 108
Typical Hold Up Time at 100W load,115/230Vac
ms 16 / 84 (see graphs for more detail)
Leakage Current µA <100µA at 100V 60Hz input, <250µA at 230V 50Hz
Touch Current (enclosure leakage) µA <100 µA
Cooling - 80W with convection cooling, 100W max. with forced air cooling (see airow rate graphs)
Efciency - Up to 90% (see efciency curves)
Operating Temperature °C -20°C to +70°C, derate linearly to 50% load from 50°C to 70°C
Storage Temperature °C -40°C to +85°C
Operational Altitude - 5000m
Overcurrent Protection hiccup (auto recovery)
Overvoltage Protection Latching (unit shutdown, recycle mains to restart)
No Load Input Power at 230Vac W <0.5
Average Active Efciency % >87
Humidity (non condensing) RH Operating and storage : 5 - 95% (non-condensing)
Withstand Voltage - Input to output 4kVac 2x MoPP, 1.5kVac input to ground 1x MoPP, 1.5kVac output to ground 1 x MoPP
Isolation Resistance - >100MΩ at 25°C & 70%RH
Isolation Class (3) Construction suitable for Class II installations
Vibration - 10 to 500Hz at 2G, EN60068-2-6 19,6m/s² Constant, X, Y, Z 1 hour each.
Shock - 30G EN60068-2-27, -47, MIL-STD-810E
Approvals -
IEC/EN/UL 60950-1, CSA22.2 No. 60950-1, IEC/EN 60601-1 (2nd & 3rd editions)
CE mark Designed to meet IEC/EN/UL/CSA 61010-1, ANSI/AAMI ES60601-1:2005 (r) 2012 CQC safety standard GB4943.1-2011 (pending)
Conducted & Radiated EMI EN55011 / EN55022 level B conducted, level A radiated
EN 61000-4-2 (Level 3 criteria A) -3 (Level 3 criteria A) -4 (Level 3 criteria A),
Immunity (5) - -5 (Level 3 criteria A), -6 (Level 3 criteria A), -8 (Level 3 criteria A), -11(class 3), -12(level 3)
Meets the requirements of EN60601-1-2:2007 (as applicable to a component power supply)
Weight (Typ) g 150
Size (W x L x H) mm 50.8 x 101.6 x 31.9
Warranty yrs 3
Connectivity
Molex as standard with separate ground faston
Input Molex 10-63-4027, output Molex 09-65-2048
Notes: 1. Specication parameters apply at 25°C ambient temperature unless stated otherwise.
2. For 12V & 15V unit derate from 100% at 100V to 90% at 90V and to 80% at 85V, for 24V, 36V, & 48V unit derate from 100% at 90V to 90% at 85V. (convection and forced air ratings) .
3. ZMS100 uses Y1 capacitors to earth. 4. Consult Sales Ofce for use under DC Input conditions
5. Criteria B for dips and interruptions, contact technical support for full details.
(1)

Summary of content (5 pages)