Datasheet
931-800-526-2324 • www.us.tdk-lambda.com/lp/ Disclaimer: us.tdk-lambda.com/lp/legal.htm
ZMS100 Series
Features
 80W Convection, 100W with Forced Air
 ITE & Medical Certifi cations (2 x MOPP) (BF Rated)
 Long Capacitor Lifetimes
 Class I and Class II operation
 Compact 2 x 4 x 1.25” Size
100W, 2 x 4” AC-DC Power Supplies
Model    ZMS100  
  Input Voltage range (1)  -  90 - 264VAC (47 - 63Hz) 
  Inrush Current (Cold start at 264VAC input)  A  <40A 
  Input Current (100W load)  A  2.0 / 1.0A (115 / 230VAC) 
  Hold Up Time (Typ)  ms  5ms at 100VAC input, 50ms at 230VAC 
  Harmonic Compliance  -  EN/IEC61000-3-2 class A 
  Leakage Current  uA  <100uA at 100VAC 60Hz input, <250uA at 230VAC 50Hz 
  Touch Current (enclosure leakage)  uA  <100uA 
 Temperature Coeffi cient  -  ±0.02%/°C 
  No Load Power Draw at 230VAC input  W  <0.5W 
  Ripple & Noise  mV (pk-pk)  ≤2% 
 Load Regulation  mV  ≤1% (0 - 100% load) 
 Line Regulation  mV  ≤0.5% (90 - 264VAC) 
  Short Circuit Protection  -  Hiccup mode, automatic recovery 
  Overvoltage Protection  V  Latching (unit shutdown), cycle AC input to reset 
 Effi ciency  %  Up to 90% 
 Active Average Effi ciency  %  >87% 
  Operating Temperature  °C  -20 to +70°C, derate linearly to 50% load from 50 to 70°C 
  Storage Temperature  °C  -40 to +85°C 
  Humidity (non condensing)  %RH  5 - 95%RH 
  Cooling  -  Convection cooling 80W
      Forced air 100W (see technical datasheet on website) 
  Withstand Voltage  VAC  Input to Ground 1.5kVAC (1xMOPP), Input to Output 4kVAC (2xMOPP), 
      Output to Ground 1.5kVAC (1xMOPP) 
  Isolation Resistance  -  >100M at 25C & 70%RH, Output to Ground 500VDC 
  Insulation Class  -  Construction suitable for Class II installation 
  Vibration (non operating)  -  10 to 500Hz at 2G, IEC610068-2-6, 19.6m/s
2
 constant sweep X, Y, Z for 1 hour 
  Shock  -  30G EN610068-2-27, -47, MIL-STD-810E 
 Safety Agency Certifi cations  -  IEC/EN/UL60950-1 and 60601-1. ES60601-1.
      Designed to meet IEC61010-1, CQC safety standard GB4943.1-2011 
  Conducted & Radiated EMI  -  EN55011 / EN55022-B conducted, -A radiated 
  Immunity  -  EN61000-4-2, -3, -4, -5, -6, -8 (Level 3 critieria A) -11 (class 3), -12 (level 3) 
 Weight (Typ)  g  150 
 Size (WxLxH)  Inch (mm)  2 x 4 x 1.26” (50.8 x 101.6 x 31.9mm) 
 Warranty  yrs  Three years
  Connectors  -  Molex as standard with separate ground faston
      Input Molex 10-63-4027, output Molex 09-65-2048
Specifi cations
Key Market Segments & Applications
1) ZMS100-12 derate linearly to 90% load from 100V to 90VAC input