Data Sheet

SWS600/1000L Series
1
SWS600/1000L Series
600W and 1000W Low Profile Single Output Power Supplies
• Quiet Temperature Controlled Fan
• Low Cost
Low Profile
• Wide Operating Temperature Range
Active Power Factor Correction
• Medical Approvals (SWS1000L)
SWS600/1000L Features and Benefits
Features Benefits
• Temperature Controlled Fan • Low Acoustic Noise
• Global safety Approvals • Supports Global Use
• Wide Temperature Range • Suitable for Outdoor Temperature Extremes
• Level B EMI Assists System Compliance
Specifications
MODEL SWS600L SWS1000L
ITEMS
Input Voltage range - 85 - 265VAC (47 - 63Hz) or 120 - 350VDC
*
Inrush Current (115 / 230VAC) A 20 / 40
Power Factor - Meets EN61000-3-2 Class A
Input Current (100/200VAC) A 7.1 / 3.6 (3.3V : 5/2.5) 12/6 (3.3V : 8/4)
Temperature Coefficient - <0.02%/°C
Overcurrent Protection - >105%, Constant current style
Overvoltage Protection V 125% -145%
Over temperature Protection - Yes, cycle AC or Remote On/Off to reset
Hold Up Time (Typ) ms 20ms at 115/230VAC
Leakage Current (max) mA <0.75mA <0.3mA
(1)
Remote Sense - Yes
Parallel Connection - Yes
Remote On/Off (CNT) - Yes
Voltage Programming - Yes, 1-6V adjusts output from 20 - 120% of nominal
DC Good & Fan Fail Signal - Yes, open collector output
Auxiliary Output - 12V 0.1A
LED Indicator - Green LED = On
Operating Temperature - -40°C start up. -20°C to 74°C, derating linearly to 50% load above 50°C
Storage Temperature - -40°C to +85°C
Humidity (non condensing) - 20 - 90% RH operating, 10 - 95%RH non operating
Cooling - Internal fan
Withstand Voltage(One minute) -
Input to Ground 2kVAC, Input to Output 3kVAC, Input to Ground 2kVAC, Input to Output 4kVAC
**
,
Output to Ground 500VAC, Output to CNT 100VAC Output to Ground 500VAC, Output to CNT 100VAC
Isolation Resistance - >50MΩ at 25°C & 70%RH, Output to Ground 500VDC
Vibration (non operating) - MIL-STD-810F 514.5 CAT. 4,10
Shock (in packaging) - MIL-STD-810F 516.5 Procedure 1, V1
Immunity - EN61000-4-2, -3, -4, -5, -6, -8, -11
Safety Agency Approvals - UL/CSA/EN 60950-1, UL/CSA/IEC/EN 60601-1 & ANSI/AAMI ES60601-1,(1000W only),
IEC61010-1 (600W only), EN50178, CE Mark
Conducted & Radiated EMI - EN55011 / EN55022-B, FCC Class B
Weight (Typ) g 1600 2300
Size (WxHxD) mm 61 x 120 x 190 61 x 150 x 240
Warranty yrs 3
Notes: (1) Worst case: <300µA at 264Vac, 63Hz (Normal condition); <500µA (Single Fault Condition).
*Safety certified for AC input only
**2 x MOPP, IEC60601-1 (3rd edition)