Data Sheet
SWS1000L
(4) Functional shock test
(MIL-STD-810F 516.5 Procedure I)
1. Purpose
Test based on [MIL-STD-810F 516.5 Procedure I - Functional shock].
2. Test method
Unit was taken directly from production line.Unit was compliant with production standards
.
The performance of vibration test machine is confirmed before vibration test.
Unit is operating during shock test.
* See the APPENDIX B [Direction of vibration]
* It does in the directions of ± X, ± Y and ± Z 3 times for each and 18 times in total.
3. Acceptable conditions
During shock test,no discharge of fire or smoke, as well as no output failure.
After shock test,no abnormality in the electric characteristics and the mechanism.
4. Test result
OK
AC115V
50Hz
Rated
Qty.
40G
Half Sine Pulse
11ms
Min.peak value
(g's)
Duration
100%
Input voltage Output voltage Output current
1pc
DENSEI-LAMBDA
R-16