6. Power Frequency Magnetic Field Immunity Test (IEC61000-4-8)
MODEL : SWS1000L
(1) Equipment Used
Test Laboratory : TUV SUD PSB Singapore Accreditation Lab.
(2) Test Conditions
Input Voltage : 115, 230VAC Output Voltage : Rated
Output Current : 100% Magnetic Frequency : 50Hz
Test Time : > 10 sec (Each direction) Ambient Temperature : 25
o
C
Direction : X, Y, Z
(3) Test Method and Device Test Point
(4) Acceptable Conditions
1. Output voltage regulation not to exceed +
5% of initial (before test) value during test.
2. Output voltage to be within output voltage regulation specification after the test.
3. Along with 1 and 2, no discharge of fire or smoke, as well as no output failure.
(5) Test Result
Magnetic Field Strength (A/m) SWS1000L-24
1 PASS
3 PASS
10 PASS
30 PASS
Helmholts Coils
1.5m
AC INPUT
LOAD
D.U.T.
Wooden Table
0.8m
Analog Voltage Mater
V
AC Power
Source
Shunt
Resistor
Signal Phase
Analyzer