Data Sheet

SWS1000L
DENSEI-LAMBDA R-5
5. Conducted Disturbances Induced by Radio-Frequency Field
Immunity Test (IEC61000-4-6)
MODEL : SWS1000L
(1) Equipment Used
Test Laboratory : TUV SUD PSB Singapore Accreditation Lab.
(2) Test Conditions
Input Voltage : 115, 230VAC Output Voltage : Rated
Output Current : 100% Electromagnetic Frequency : 150kHz~80MHz
Ambient Temperature : 25°C
Sweep Conditions : 1.0% Step Up, 3.0 Seconds Hold
(3) Test Method
(4) Acceptable Conditions
1. Output voltage regulation not to exceed ±5% of initial (before test) value during test.
2. Output voltage to be within regulation specification after the test.
3. Along with 1 and 2, no discharge of fire or smoke, as well as no output failure.
(5) Test Results
Test Voltage (V) SWS1000L-24
1 PASS
3 PASS
10 PASS
Aluminium Plate
Wooden Table
LOAD
D.U.T
GND
FG
V
CDN
AC INPUT
RF INPUT
FG
Analog Voltage Meter
10cm
GND Plane
10 ~ 30 cm