Instructions
Table Of Contents
- LS50(75(100(150 Series
- Instruction Manual
- 1. Terminal Explanation
- LS50, LS75
- 2. Terminal connecting method
- LS50, LS75 LS100, LS150
- Maximum output current of each output terminal is 25A. If more than 25A, use 2 terminals
- 3. Explanation of Functions and Precautions
- 3-1. Input Voltage Range
- 3-2. Output Voltage Range
- 3-3. Inrush Current
- 3-4. Over Voltage Protection (OVP)
- 3-5. Over Current Protection (OCP)
- 3-6. Output Ripple & Noise
- 3-7. Series Operation
- 3-8. Parallel Operation
- 4. Isolation / Withstand Voltage
- 4-1. Isolation Test
- 4-2. Withstand Voltage
- 5-1. Output Derating according to the Mounting Directions
- NOTE : LS50, LS75 & LS150 series do not require Input Voltage Derating.
- 5-2 Mounting Method
- Note 1 : When using separate loads, use of two pcs of 0.8mm thick crimp-type terminal is recommended.
- 7. External Fuse Rating
- 8. Before concluding that the unit is at fault…

NEMIC-LAMBDA
LS50
⋅
75
⋅
100
⋅
150 Series
INSTRUCTION MANUAL
4. Isolation / Withstand Voltage
4-1. Isolation Test
Isolation resistance between output and FG (chassis) shall be more than 100MΩ at 500VDC. For safety, voltage setting
of DC isolation tester must be done before the test. Ensure that the unit is fully discharged after the test.
(a) Output ~ FG (chassis) : 500VDC, 100MΩ or more
AC(L)
AC(N)
FG
+ V
+V
- V
- V
Isolation
Tester
4-2. Withstand Voltage
This series is designed to withstand 3.0kVAC between input and output, 1.5kVAC between input and FG (chassis) and
500VAC between output and FG (chassis) each for 1 minute. When testing withstand voltage, set current limit of with-
stand voltage test equipment at 20mA ( Output-FG (chassis) : 100mA ). The applied voltage must be gradually increased
from zero to testing value and then gradually decreased for shut down. When timer is used, the power supply may be
damaged by high impulse voltage at timer switch on and off. Connect input and output as follows :
(a) Input ~ FG (chassis) : solid line (c) Output ~ FG (chassis) : 500VAC, 1min (100mA)
1.5kVAC, 1min (20mA)
(b) Input ~ Output : dotted line
3kVAC, 1min ( 20mA )
AC(L)
AC(N)
FG
+V
+V
-V
-V
Withstand
Voltage
Tester
AC(L)
AC(N)
FG
+V
+V
-V
-V
Withstand
Voltage
Tester
4