5. Mounting Directions 
5-1. Output Derating according to the Mounting Directions 
Recommended standard mounting is Method ( A ). Method ( B ), ( C ) and ( D ) are also possible. Refer to the derating 
below. Please do not use installation Method ( E ), where the PCB will be on the topside and heat will be trapped inside 
the unit. 
In the following derating curve, the maximum output current is considered to be 100%. 
(A) Output Derating versus Ambient Temperature (Convection Cooling) 
LS50-3.3, -5, -12, -15, -24, -36 & -48   
Output Derating Vs Ambient Temperature
0 
20 
40 
60 
80 
100 
120 
-25  0  25  50 75
100
Ambient Temperature (°C)
Load 
Mounting
 Mounting
 A, B & D 
 C 
40 60 
70 
50 
70 
5 