Datasheet
161-800-526-2324 • www.us.tdk-lambda.com/lp/ Disclaimer: us.tdk-lambda.com/lp/legal.htm
HWS-/HD Series
Features
Limited Lifetime Warranty
-10 to +71°C Operation (-40°C start up)
Universal Input (85 - 265VAC)
Conformally coated pcbs
Class 1 Div 2 option (/RYHD suffi x)
30-1500W Single Output Industrial Power Supplies
Specifi cations
(1) 100/200VAC input
(2) HWS300-600 2.5kVAC Input to ground
(3) 1-6V program voltage input to adjust output 20-120% (typical) of nominal. See instruction manual for details & models with this feature
(4) No DC Input for HWS1500
* Class 1 Div 2 option (/RYHD suffi x)
** Safety certifi ed for AC input only. DC input not available on HWS1500
*** 24V output model, 25°C ambient, full load, 230VAC input
Key Market Segments & Applications
Model HWS30A HWS50A HWS100A HWS150A HWS300 HWS600 HWS1000 HWS1500
Input Voltage range (47-63Hz) - 85 - 265VAC or 120 - 370VDC** 85-265VAC or 120 - 330VDC**(4)
Input Current (Typ) (1) A 0.65 / 0.4 0.7 / 0.35 1.3 / 0.65 1.9 / 0.95 4.1 / 2.1 8.1 / 3.9 13.5 / 7 19 / 10
Inrush Current (1) A 14 / 28 20 / 40
Power Factor - Meets EN61000-3-2
Temperature Coeffi cient - <0.02%/°C
Overcurrent Protection - >104%
Overvoltage Protection V Yes (See table on page 2)
Hold Up Time (Typ) ms 20
Leakage Current (60Hz) mA <0.5mA <0.75mA <1.2mA <1.5mA
Remote Sense - No Yes
Indicator - Green LED = ON
Remote On/Off - No Yes (Isolated from output)
Parallel operation - No Single wire connection (5 units max)
DC Good - No Yes
Remote Adjust (PV) - No Yes (3)
Operating Temperature °C HWS50-150: -10 to +71°C, (Derating applies above 50°C)
and Derating HWS300-1500: -10°C~+71°C, (Derate linearly to 50% load from +50~+71°C)
Guaranteed start up at -40°C (see specifi cation sheets on website for details and derating)
Storage Temperature °C -40 to +85°C
Humidity (non condensing) - Operating: 30 - 90%RH (10 -90% on HWS300-1500), Non operating 10 - 95%RH
Cooling - Convection Internal fan
Withstand Voltage (2) - Input to Ground 2kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min.
Isolation Resistance - >100MΩ at 25°C & 70%RH, Output to Ground 500VDC, >10M Output to remote on/off 100VDC
Vibration (non operating) - MIL-STD-810F 514.5 Category 4, 10 (HWS1500 Cat 4, fi gure 514.5C-1)
Shock (in packaging) - MIL-STD-810F 516.5 Category I, VI (HWS1500 <196.1m/s
2
)
Safety Agency Approvals - UL60950-1, CSA60950-1, EN60950-1, CE Mark
Line Dips - SEMI-F47 (200VAC input)
Conducted & Radiated EMI - EN55011 / EN55022-B, FCC-B, VCCI-B (HWS1500 Class A)
Immunity IEC61000-4-2, -3, -4, -5, -6, -8, -11, IEC61000-6-2
Weight (Typ) g 200 260 420 470 1000 1600 3200 3800
Size (WxHxD) in 1.04x3.23x3.74 1.04x3.23x4.72 1.1x3.23x6.3 1.46x3.23x6.3 2.4x3.23x6.5 3.94x3.23x6.5 5x3.2x9.5 5x3.25x11
MTBF - Telcordia SR-332 issue 3** hours 8,169,868 3,726,622 2,963,512 2,676,081 2,145,809 1,998,996 1,087,031 1,152,309