Datasheet

GXE600 Series
,QGXVWULDO 7HVW
Single Output 600W Programmable
Medical & ITE Power Supplies
GXE600 Series
1
www.emea.tdk-lambda.com/gxe600
&RPP
%URDGFDVW
Features Benets
•ConvectionCooled •LowAcousticNoiseandVibration
•Upto95%Efcient •LessPowerConsumed
•ConstantVoltage&ConstantCurrentModes •CanbeusedasaVoltageorCurrentSource
•Monitoring&ProgrammingFunctions •Read/writeCapabilityforFlexibility
•DigitalorAnalogProgramming •ForusewithRS-485oranExternalVoltage
•SevenYearWarranty •LowCostofOwnership
0HGLFDO
Notes: (1)85Vac:360W,100to<170Vac:500W,170Vto265Vac:600W(Convectioncooled).600Wwhenforcedairisapplied(seeinstallationmanual)
(2)UsingRS-485communicationsorexternal1-6Vvoltagesource.Seeinstallationmanualfordetails
(3)Overcurrent&OvervoltagelimitsandrecoverymodescanbesetusingtheRS-485communications
4)Seeinstallationmanualforfullderatingcurves*24Voutputmodel,25°Cambient,fullload,230VACinput
Specication
Model GXE600-24 GXE600-48
ACInputVoltagerange
(1)
VAC 85-265VAC(47-63Hz).Withstands300VACfor5s
InrushCurrent(100/200VAC) A 40/40A
PowerFactor(100/200VAC) - MeetsEN61000-3-2(0.99/0.95)
InputCurrent(115/230VAC)(Typ) A 6.1/3.1A
NominalOutputVoltage VDC 24V 48V
MaximumOutputCurrent A 25A 12.5A
OutputVoltageRange
(ManualAdjust)
VDC 19.2-28.8V 38.4-57.6V
OutputVoltageRange
(ViaProgramming)
(2)
VDC 4.8-28.8V 9.6-57.6V
CurrentLimitSetPoint
(ViaProgramming)
(2)
A 5-28.8A 2.5-14.4A
TemperatureCoefcient %/°C <0.02%/°C
Regulation - SeeModelSelector
OvercurrentProtection
(3)
- >28.8A >14.4A
OvervoltageProtection
(3)
V 28.8-31.2V 57.6-62.4V
HoldUpTime(Typat100%load) ms 20ms
LeakageCurrent(max) mA <0.3mA
StandbyVoltageVsb) - 4.8V-5.2V1A
RemoteSense - Yes
RemoteOn/Off - Isolatedopto-coupler.Unitoffwhencurrentisowingthroughtheoptodiode
PowerFailSignal - SignalishighwhentheoutputvoltagedropsduetoAClossorOCP,OVP,OTP
ACFailSignal - SignalgoeshighwhentheACinputisnotpresent
ParallelOperation - Yes,uptoveunits
OperatingTemperature(-40°Cstartup) °C Convection:-20°Cto+70°C,deratelinearlyto50%loadfrom50°Cto70°C
(4)
StorageTemperature °C -40°Cto+85°C
OperatingHumidity(noncondensing) %RH 20-90%RH
StorageHumidity(noncondensing) %RH 10-90%RH
Cooling - Convectionorforcedaircooling
WithstandVoltage VAC
InputtoGround2kVAC(1xMOPP),InputtoOutput4kVAC(2xMOPP),
OutputtoGround1.5kVAC(1xMOPP),OutputtoSignals100VACfor1min.
IsolationResistance MΩ >100MΩat25°C&70%RH,OutputtoGround500VDC
Vibration(nonoperating) - 10-55Hz:19.6m/s
2
(sweep1min)X,Y,Zfor1hour
Shock - <196.1m/s
2
SafetyAgencyCertications -
IEC/UL/CSA/EN60950-1,IEC/UL/CSA/EN62368-1,IEC/ES/CSA/EN60601-1,
IEC/EN62477-1(OVCIII),CEMark
LineDips - SEMI-F47(200VACinput)
Conducted&RadiatedEMI - EN55011/EN55032-B,FCCClassB,VCCI-B
Immunity - IEC61000-4-2,-3,-4,-5,-6,-8,-11,IEC61000-6-2,IEC60601-1-2Ed4
Weight(Typ) g 1300
Size(WxHxD) mm 127x41x254mm
MTBF-TelcordiaSR-332issue3* Hours 511,677hours
Warranty Yrs 7