Data Sheet
GWS500 Series
3
GWS500OutputVoltageExternalControl(PV)
Output voltage external control function is available. Output voltage can be varied by applying an external voltage (3–6V) to “PV” terminal and “COM” terminal.
Seeinstructionmanualfordetails.
Output Derating Curve GWS500 Mounting Options GWS500 /L /F options
12
TDK-Lambda
GWS
500
Series
INSTRUCTION MANUAL
6. Mounting Directions
6-1. Output Derating according to the Mounting Directions
Recommended standard mounting is Method ( A ). Method ( B ) is also possible.
Refer to the Derating below.
(A) Standard Mounting (B)
6-2. Output Derating
For /L and /P option, the system is forced air cooling with external airflow of at least 15cfm and air blowing out from the
opposite side of the input/output connectors.
70
50
Airflow
(≥ 15 cfm)
OUTPUT DERATING CURVE
0
20
40
60
80
100
120
-25 0 25 50 75 100
Ta (
o
C)
LOAD (%)
MOUNTING
A,B
70
50
For /L and /F option, the system is forced air cooling with
external airow of at least 15cfm and air blowing out from
the opposite side of the input/output connectors.
Airow
≥15cfm
12
TDK-Lambda
GWS
500
Series
INSTRUCTION MANUAL
6. Mounting Directions
6-1. Output Derating according to the Mounting Directions
Recommended standard mounting is Method ( A ). Method ( B ) is also possible.
Refer to the Derating below.
(A) Standard Mounting (B)
6-2. Output Derating
For /L and /P option, the system is forced air cooling with external airflow of at least 15cfm and air blowing out from the
opposite side of the input/output connectors.
70
50
Airflow
(≥ 15 cfm)
OUTPUT DERATING CURVE
0
20
40
60
80
100
120
-25 0 25 50 75 100
Ta (
o
C)
LOAD (%)
MOUNTING
A,B
70
50
Note: Allow at least 50mm clearance at each end for adequate airow.
/L version must have at least 4mm clearance above the unit to
comply with Safety Approvals
50mm
4mm/Lversion
50mm
Options
Sufx Description
/ T OTP auto recovery after unit cools down
/ RL Remote ON/OFF reverse logic (Active High)
/ BAT Battery charging for 24V (21~29V/17.6A) & 48V (42~58V/8.8A) only
/ F Full cover without internal fan but require external forced air cooling
/ L Without cover but require external forced air cooling
/ CO2 Double side coated pcb
MOQsapplytoOptionmodels
Please contact your local TDK-Lambda sales ofce for details.