Data Sheet

Genesys ™ 3.3kW Specifications
*1:Minimumvoltageisguaranteedtomaximum0.2%ofratedoutputvoltage.
*2:Minimumcurrentisguaranteedtomaximum0.4%ofratedoutputcurrent.
*3:Forcaseswhereconformancetovarioussafetystandards(UL,IEC,etc›)isrequired,tobe
describedas190-240Vac(50/60Hz)forsinglephaseand3-Phase208Vmodels,and380~415Vac
(50/60Hz)for3-Phase400Vmodels.
*4:Single-Phaseand3-Phase208Vmodels:At208Vacinputvoltage,3-Phase400V:At380Vac
inputvoltage.Withratedoutputpower.
*5:NotincludingEMIfilterinrushcurrent,lessthan0.2mSec.
*6:Single-Phaseand3-Phase208Vmodels:170~265Vac,constantload.3-Phase400Vmodels:
342~460Vac,constantload.
*7:FromNo-LoadtoFull-Load,constantinputvoltage.MaximumdropinRemoteSense.
*8:For8V~300Vmodels:MeasuredwithJEITARC-9131A(1:1)probe.
For600Vmodel:Measuredwith10:1probe.
*9:From10%to90%or90%to10%ofRatedOutputVoltage,withrated,resistiveload.
*10:From90%to10%ofRatedOutputVoltage.
*11:Forloadvoltagechange,equaltotheunitvoltagerating,constantinputvoltage.
*12:For8V~15Vmodelstherippleismeasuredfrom2Vtoratedoutputvoltageandratedoutput
current.Forothermodels,therippleismeasuredat10~100%ofratedoutputvoltageandrated
output current.
*13:TheConstantCurrentprogrammingreadbackandmonitoringaccuracydoesnotincludethe
warm-upandLoadregulationthermaldrift.
1.0 MODEL
MODEL GEN 8-400 10-330 15-220 20-165 30-110 40-85 60-55 80-42 100-33 150-22 200-16.5 300-11
600-5.5
1.Ratedoutputvoltage(*1) V 8 10 15 20 30 40 60 80 100 150 200 300 600
2.RatedOutputCurrent(*2) A 400 330 220 165 110 85 55 42 33 22 16.5 11 5.5
3.RatedOutputPower W 3200 3300 3300 3300 3300 3400 3300 3360 3300 3300 3300 3300 3300
1.1 CONSTANT VOLTAGE MODE
1.Max.lineregulation(0.01%ofratedVo+2mV)(*6)
mV 2.8 3 3.5 4 5 6 8 10 12 17 22 32 62
2.Maxloadregulation(0.015%ofratedVo+5mV)(*7)
mV 6.2 6.5 7.25 8 9.5 11 14 17 20 27.5 35 50 95
3.Rippleandnoisep-p20MHz(*8) mV 60 60 60 60 60 60 60 80 100 100 275 300 500
4.Rippler.m.s5Hz~1MHz mV 8 8 8 8 8 8 8 25 25 25 75 100 120
5.Remotesensecompensation/wire V 2 2 2 2 5 5 5 5 5 5 5 5 5
6.Temp.coefficient
PPM/°C
100PPMCofratedoutputvoltage,following30minuteswarm-up
7.Temp.stability 0.05%ofratedVoutover8hrsintervalfollowing30minuteswarm-up.Constantline,load&temp.
8.Warm-updrift Lessthan0.05%ofratedoutputvoltage+2mVover30minutesfollowingpowerOn.
9.Up-prog.responsetime,0~VoRated(*9) mS 80 150 200 250
10.Down-progresponsetime
Full-load(*9) mS 20 100 160 300 500
No-load(*10) mS 500 600 700 800 900 1000 1100 1200 1500 2000 3000 3500 4000
11.Transientresponsetime mS
Timeforoutputvoltagetorecoverwithin0.5%ofitsratedoutputforaloadchange10-90%ofratedoutputcurrent.Output
set-point:10-100%,localsense.Lessthan1mSecformodelsuptoandincluding100V.2msecformodelsabove100V
1.2 CONSTANT CURRENT MODE
1.Max.lineregulation(0.01%ofratedIo+2mA)(*6)
mA 42 35 24 18.5 13 10.5 7.5 6.2 5.3 4.2 3.65 3.1 2.6
2.Max.loadregulation(0.02%ofratedIo+5mA)(*11)
mA 85 71 49 38 27 22 16 13.4 11.6 9.4 8.3 7.2 6.1
3.Rippler.m.s5Hz~1MHz.(*12) mA 1300 1200 880 660 300 200 100 80 70 60 40 20 10
4.Loadregulationthermaldrift Lessthan0.1%ofratedoutputcurrentover30minutesfollowingloadchange.
5.Temp.coefficient
PPM/°C
100PPMCfromratedoutputcurrent,following30minuteswarm-up.
6.Temp.stability 0.05%ofratedIoutover8hrs.intervalfollowing30minuteswarm-up.Constantline,load&temperature.
7.Warm-updrift
8V~20Vmodels:Lessthan±0.5%ofratedoutputcurrentover30minutesfollowingpowerOn.
30V~600Vmodels:Lessthan±0.25%ofratedoutputcurrentover30minutesfollowingpowerOn.
1.3 PROTECTIVE FUNCTIONS
1.OCP 0~105%ConstantCurrent
2.OCPFoldback OutputshutdownwhenpowersupplychangefromCVtoCC.Userselectable.
3.OVPtype
Invertershut-down,manualresetbyACinputrecycleorbyOUTbuttonorbycommunicationportcommand.
4.OVPtrippoint
0.5~10V
0.5~12V
1~18V 1~24V 2~36V 2~44V 5~66V 5~88V 5~110V 5~165V 5~220V 5~330V 5~660V
5.OutputUnderVoltageLimit Presetbyfrontpanelorcommunicationport.PreventsfromadjustingVoutbelowlimit.
6.OverTemp.Protection Userselectable,latchedornon-latched.
1.4 ANALOG PROGRAMMING AND MONITORING
1.VoutVoltageProgramming 0~100%,0~5Vor0~10V,userselect.Accuracyandlinearity0.5%ofratedVout.
2.IoutVoltageProgramming(*13) 0~100%,0~5Vor0~10V,userselect.Accuracyandlinearity:±1%ofratedIout.
3.VoutResistorProgramming 0~100%,0~5/10Kohmfullscale,userselect.,Accuracyandlinearity:±1%ofratedVout.
4.IoutResistorProgramming(*13) 0~100%,0~5/10Kohmfullscale,userselect.Accuracyandlinearity:±1.5%ofratedIout.
5.On/Offcontrol(rearpanel) Byelectrical.Voltage:0~0.6V/2~15V,ordrycontact,userselectablelogic.
6.OutputCurrentmonitor(*13) 0~5Vor0~10V,Accuracy1%,userselectable.
7.OutputVoltagemonitor 0~5Vor0~10V,Accuracy1%,userselectable.
8.PowerSupplyOKsignal TTLhigh(4~5V)-OK,0V-Fail500ohmseriesresistance.
9.CV/CCIndicator Opencollector,CCmode:On,CVmode:Off,Maximumvoltage:30V,maximumsinkcurrent:10mA
10.Enable/Disable Drycontact.Open:off,Short:on.Max.voltageatEnable/Disablein:6V.
11.Local/Remoteanalogcontrol ByelectricalsignalorOpen/Short:0~0.6Vorshort:Remote,2~15Voropen:Local.
12.Local/RemoteanalogcontrolIndicator Opencollector,Local:Off,Remote:On.Maximumvoltage:30V,maximumsinkcurrent:10mA.
1.5 FRONT PANEL
1.Controlfunctions
Vout/Ioutmanualadjustbyseparateencoders(coarseandfineadjustmentselectable).
OVP/UVLmanualadjustbyVolt.Adjustencoder.
On/Off,Outputon/off,Re-startmodes(auto,safe),Foldbackcontrol(CVtoCC),Gotolocalcontrol.
AddressselectionbyVoltage(orcurrent)adjustencoder.Numberofaddresses:31.
Re-startmodes(automaticrestart,safemode).
Baudrateselection:1200,2400,4800,9600and19,200.
2.Display
Voltage:4digits,Accuracy:0.5%ofratedoutputVoltage±1count.
Current:4digits,Accuracy:0.5%ofratedoutputcurrent±1count.
3.Indications Voltage,Current,Alarm,Fine,Preview,Foldback,Local,OutputOn,FrontPanelLock,CVCC.
1.6 Interface Specifications for the GENESYS Series with RS-232/RS-485 Or Optional GPIB/LAN Interface Installed
1.RemoteVoltageProgramming(16bit) V 8 10 15 20 30 40 60 80 100 150 200 300 600
Resolution(0.012%ofVoRated) mV 0.96 1.2 1.8 2.40 3.60 4.80 7.2 9.6 12 18 24 36 72
Accuracy(0.05%VoRated+0.05%ofVoActualOutput)
mV 8 10 15 20 30 40 60 80 100 150 200 300 600
2.RemoteCurrentProgramming(16bit)
Resolution(0.012%ofIoRated) mA 48 39.6 26.4 19.8 13.2 10.2 6.6 5.0 4.0 2.6 2.0 1.3 0.7
Accuracy(0.2%ofIoRated+0.1%ofIoActualOutput)(*13)
mA 1200 990 660 495 330 255 165 126 99 66 49.5 33 16.5
3.ReadbackVoltage
Resolution(0.012%ofVoRated) mV 0.96 1.2 1.8 2.40 3.60 4.80 7.2 9.6 12 18 24 36 72
Accuracy(0.1%VoRated+0.1%ofVoActualOutput)
mV 16 20 30 40 60 80 120 160 200 300 400 600 1200
4.ReadbackCurrent
Resolution(0.012%ofIoRated) mA 48 39.6 26.4 19.8 13.2 10.2 6.6 5.0 4.0 2.6 2.0 1.3 0.7
Accuracy(0.3%ofIoRated+0.1%ofIoActualOutput)(*13)
mA 1600 1320 880 660 440 340 220 168 132 88 66 44 22
5.OVP/UVLProgramming
Resolution(0.1%ofVoRated) mV 8 10 15 20 30 40 60 80 100 150 200 300 600
Accuracy(1%ofVoRated) mV 80 100 150 200 300 400 600 800 1000 1500 2000 3000 6000
4 | GENESYS | 3.3kW