Data Sheet
Genesys ™ 5kW Specifications
*1:Minimumvoltageisguaranteedtomaximum0.2%ofratedoutputvoltage.
*2:Minimumcurrentisguaranteedtomaximum0.4%ofratedoutputcurrent.
*3:Forcaseswhereconformancetovarioussafetystandards(UL,IEC,etc›)isrequired,tobe
describedas190-240Vac (50/60Hz)for3-Phase208Vmodels,and380~415Vac (50/60Hz)for
3-Phase400Vmodels.
*4:3-Phase208Vmodels:At208Vacinputvoltage,3-Phase400V:At380Vacinputvoltage.With
rated output power.
*5:NotincludingEMIfilterinrushcurrent,lessthan0.2mSec.
*6: 3-Phase208Vmodels:170~265Vac, constantload. 3-Phase 400V models: 342~460Vac,
constant load.
*7:FromNo-LoadtoFull-Load,constantinputvoltage.MaximumdropinRemoteSense.
*8:For8V~300Vmodels:MeasuredwithJEITARC-9131A(1:1)probe.
For600Vmodel:Measuredwith10:1probe.
*9:From10%to90%or90%to10%ofRatedOutputVoltage,withrated,resistiveload.
*10:From90%to10%ofRatedOutputVoltage.
*11:Forloadvoltagechange,equaltotheunitvoltagerating,constantinputvoltage.
*12:For8V~16Vmodelstherippleismeasuredfrom2Vtoratedoutputvoltageandratedoutput
current.Forothermodels,therippleismeasuredat10~100%ofratedoutputvoltageandrated
output current.
*13:TheConstantCurrentprogrammingreadbackandmonitoringaccuracydoesnotincludethe
warm-upandLoadregulationthermaldrift.
1.0 MODEL
MODEL GEN 8-600 10-500 16-310 20-250 30-170 40-125 60-85 80-65 100-50 150-34 200-25 300-17 400-13 500-10 600-8.5
1.Ratedoutputvoltage(*1) V 8 10 16 20 30 40 60 80 100 150 200 300 400 500 600
2.RatedOutputCurrent(*2) A 600 500 310 250 170 125 85 65 50 34 25 17 13 10 8.5
3.RatedOutputPower W 4800 5000 4960 5000 5100 5000 5100 5200 5000 5100 5000 5100 5200 5000 5100
1.1CONSTANTVOLTAGEMODE
1.Max.lineregulation(0.01%ofratedVo)(*6)
mV 0.8 1.0 1.6 2 3 4 6 8 10 15 20 30 40 50 60
2.Maxloadregulation(0.015%ofratedVo+5mV)(*7)
mV 6.2 6.5 7.4 8 9.5 11 14 17.7 20 27.5 35 50 65 80 95
3.Rippleandnoisep-p20MHz(*8) mV 75 75 75 75 75 75 75 100 100 120 220 300 350 400 500
4.Rippler.m.s5Hz~1MHz mV 10 10 10 10 10 10 10 15 15 25 45 60 80 100 120
5.Remotesensecompensation/wire V 2 2 2 2 5 5 5 5 5 5 5 5 5 5 5
6.Temp.coefficient
PPM/°C
100PPM/°Cofratedoutputvoltage,following30minuteswarm-up
7.Temp.stability 0.05%ofratedVoutover8hrsintervalfollowing30minuteswarm-up.Constantline,load&temp.
8.Warm-updrift Lessthan0.05%ofratedoutputvoltage+2mVover30minutesfollowingpowerOn.
9.Up-prog.responsetime,0~VoRated(*9)
mS 30 50 65 80 100
10.Down-prog
response time
Full-load(*9) mS 15 50 80 100 135 170 200
No-load(*10) mS 400 500 600 700 800 900 1000 1100 1200 1500 2000 2500 3000 3000 3000
11.Transientresponsetime mS
Timeforoutputvoltagetorecoverwithin0.5%ofitsratedoutputforaloadchange10-90%ofratedoutputcurrent.Outputset-
point:10-100%,localsense.Lessthan1mSecformodelsuptoandincluding100V.2msecformodelsabove100V
1.2 CONSTANT CURRENT MODE
1.Max.lineregulation(0.05%ofratedIo)(*6)
mA 300 250 155 125 85 62.5 42.5 32.5 25 17 12.5 8.5 6.5 5 4.25
2.Max.loadregulation(0.1%ofratedIo)(*11)
mA 600 500 310 250 170 125 85 65 50 34 25 17 13 10 8.5
3.Rippler.m.s5Hz~1MHz.(*12) mA 1950 1800 1400 1000 460 300 150 120 100 90 60 30 25 20 15
4.Loadregulationthermaldrift Lessthan0.1%ofratedoutputcurrentover30minutesfollowingloadchange.
5.Temp.coefficient
PPM/°C
100PPM/ºCfromratedoutputcurrent,following30minuteswarm-up.
6.Temp.stability 0.05%ofratedIoutover8hrs.intervalfollowing30minuteswarm-up.Constantline,load&temperature.
7.Warm-updrift
8V~16Vmodels:Lessthan±0.5%ofratedoutputcurrentover30minutesfollowingpowerOn.
20V~600Vmodels:Lessthan±0.25%ofratedoutputcurrentover30minutesfollowingpowerOn.
1.3 PROTECTIVE FUNCTIONS
1.OCP 0~105%ConstantCurrent
2.OCPFoldback OutputshutdownwhenpowersupplychangefromCVtoCC.Userselectable.
3.OVPtype Invertershut-down,manualresetbyACinputrecycleorbyOUTbuttonorbycommunicationportcommand.
4.OVPtrippoint
0.5~10V
0.5~12V 1~19V 1~24V 2~36V 2~44V 5~66V 5~88V 5~110V 5~165V 5~220V 5~330V 5~440V 5~550V 5~660V
5.OutputUnderVoltageLimit Presetbyfrontpanelorcommunicationport.PreventsfromadjustingVoutbelowlimit.
6.OverTemp.Protection Userselectable,latchedornon-latched.
1.4 ANALOG PROGRAMMING AND MONITORING
1.VoutVoltageProgramming 0~100%,0~5Vor0~10V,userselect.Accuracyandlinearity:±0.5%ofratedVout.
2.IoutVoltageProgramming(*13) 0~100%,0~5Vor0~10V,userselect.Accuracyandlinearity:±1%ofratedIout.
3.VoutResistorProgramming 0~100%,0~5/10Kohmfullscale,userselect.,Accuracyandlinearity:±1%ofratedVout.
4.IoutResistorProgramming(*13) 0~100%,0~5/10Kohmfullscale,userselect.Accuracyandlinearity:±1.5%ofratedIout.
5.On/Offcontrol(rearpanel) Byelectrical.Voltage:0~0.6V/2~15V,ordrycontact,userselectablelogic.
6.OutputCurrentmonitor(*13) 0~5Vor0~10V,Accuracy:±1%,userselectable.
7.OutputVoltagemonitor 0~5Vor0~10V,Accuracy:±1%,userselectable.
8.PowerSupplyOKsignal TTLhigh(4~5V)-OK,0V-Fail500ohmseriesresistance.
9.CV/CCIndicator Opencollector,CCmode:On,CVmode:Off,Maximumvoltage:30V,maximumsinkcurrent:10mA
10.Enable/Disable Drycontact.Open:off,Short:on.Max.voltageatEnable/Disablein:6V.
11.Local/Remoteanalogcontrol ByelectricalsignalorOpen/Short:0~0.6Vorshort:Remote,2~15Voropen:Local.
12.Local/RemoteanalogcontrolIndicator Opencollector,Local:Off,Remote:On.Maximumvoltage:30V,maximumsinkcurrent:10mA.
1.5 FRONT PANEL
1.Controlfunctions
Vout/Ioutmanualadjustbyseparateencoders(coarseandfineadjustmentselectable).
OVP/UVLmanualadjustbyVolt.Adjustencoder.
On/Off,Outputon/off,Re-startmodes(auto,safe),Foldbackcontrol(CVtoCC),Gotolocalcontrol.
AddressselectionbyVoltage(orcurrent)adjustencoder.Numberofaddresses:31.
Re-startmodes(automaticrestart,safemode).
Baudrateselection:1200,2400,4800,9600and19,200.
2.Display
Voltage:4digits,Accuracy:0.5%ofratedoutputVoltage±1count.
Current:4digits,Accuracy:0.5%ofratedoutputcurrent±1count.
3.Indications Voltage,Current,Alarm,Fine,Preview,Foldback,Local,OutputOn,FrontPanelLock,CVCC.
1.6 Interface Specifications for the GENESYS Series with RS-232/RS-485 Or Optional GPIB/LAN Interface Installed
1.RemoteVoltageProgramming(16bit)
V 8 10 16 20 30 40 60 80 100 150 200 300 400 500 600
Resolution(0.012%ofVoRated) mV 0.96 1.2 1.92 2.40 3.60 4.80 7.2 9.6 12 18 24 36 48 60 72
Accuracy(0.1%ofVoRated) mV 8 10 16 20 30 40 60 80 100 150 200 300 400 500 600
2.RemoteCurrentProgramming(16bit)
Resolution(0.012%ofIoRated) mA 72 60 37.2 30 20.4 15 10.2 7.8 6.0 4.08 3.0 2.04 1.56 1.2 1.02
Accuracy(0.3%ofIoRated+0.1%ofIoActualOutput)(*13)
mA 2400 2000 1240 1000 680 500 340 260 200 136 100 68 52 40 34
3.ReadbackVoltage
Resolution(0.012%ofVoRated) mV 0.96 1.2 1.92 2.40 3.60 4.80 7.2 9.6 12 18 36 36 48 60 72
Accuracy(0.15%VoRated) mV 12 15 24 30 45 60 90 120 150 225 450 600 800 1000 1200
4.ReadbackCurrent
Resolution(0.012%ofIoRated) mA 72 60 37.2 30 20.4 15 10.2 7.8 6.0 4.08 3.0 2.04 1.56 1.2 1.02
Accuracy(0.4%ofIoRated)(*13) mA 2400 2000 1240 1000 680 500 340 260 200 136 100 68 52 40 34
5.OVP/UVLProgramming
Resolution(0.1%ofVoRated) mV 8 10 16 20 30 40 60 80 100 150 200 300 400 500 600
Accuracy(1%ofVoRated) mV 80 100 160 200 300 400 600 800 1000 1500 2000 3000 4000 5000 6000
4 | GENESYS™ | 5kW