Programmable DC Power Supplies 5kW in 2U Built in RS-232 & RS-485 Interface Advanced Parallel Operation Optional Interface: Compliant LAN IEEE488.
The Genesys™ family of programmable power supplies sets a new standard for flexible, reliable, AC/DC power systems in OEM, Industrial and Laboratory applications.
Front Panel Description 4 1 2 6 5 3 8 7 1. ON/OFF Switch 2. Air Intake allows zero stacking for maximum system flexibility and power density. 3. Reliable encoder controls Output Voltage, Address, OVP and UVL settings. 4. Volt Display shows Output Voltage and directly displays OVP, UVL and Address settings. 5. Reliable encoder controls Output Current, sets baudrate and Advanced Parallel mode. 6. Current Display shows Output Current and displays Baud rate.
Genesys ™ 5kW Specifications 1.0 MODEL MODEL GEN 8-600 10-500 16-310 20-250 30-170 40-125 60-85 80-65 100-50 150-34 200-25 300-17 400-13 500-10 600-8.5 1.Rated output voltage(*1) V 8 10 16 20 30 40 60 80 100 150 200 300 400 500 600 2.Rated Output Current(*2) A 600 500 310 250 170 125 85 65 50 34 25 17 13 10 8.5 3.Rated Output Power W 4800 5000 4960 5000 5100 5000 5100 5200 5000 5100 5000 5100 5200 5000 5100 1.1 CONSTANT VOLTAGE MODE 1.Max.line regulation ( 0.01% of rated Vo )(*6) mV 0.8 1.0 1.
General Specifications Genesys™ 5kW 2.1 INPUT CHARACTERISTICS GEN 8-600 10-500 16-310 20-250 30-170 40-125 60-85 80-65 100-50 150-34 200-25 300-17 400-13 500-10 600-8.5 3-Phase, 208V models: 170~265Vac, 47~63Hz 3-Phase, 400V models: 342~460Vac, 47~63Hz 21 22 22 22 22 22 22 22 22 22 22 22 22 22 22 2. Maximum Input 3-Phase, 208V models: current at 100% load 3-Phase, 400V models: 10.5 11 11 12 11 11 11 11 11 11 11 11 11 11 11 3. Power Factor (Typ) 3-Phase models: 0.94@208/380Vac, rated output power. 4.
Genesys™ Power Parallel and Series Configurations Parallel operation - Master/Slave: Active current sharing allows up to four identical units to be connected in an auto-parallel configuration for four times the output power. In Advanced Parallel Master/Slave Mode, total current is programmed and reported by the Master, Up to four supplies act as one. Series operation Up to two units may be connected in series to increase the output voltage or to provide bipolar output. (Max 600V to Chassis Ground).
Power Supply Identification / Accessories How to order GEN Series Name 8 - 600 Output Voltage (0~8V Output Current (0~600A) Models 5kW Model GEN 8-600 GEN 10-500 GEN 16-310 GEN 20-250 GEN 30-170 GEN 40-125 Output Voltage VDC 0~8V 0~10V 0~16V 0~20V 0~30V 0~40V Factory option Output Current (A) 0~600 0~500 0~310 0~250 0~170 0~125 Factory Options: Option: IEEE IS510 IS420 LAN Output Power (W) 4800 5000 4960 5000 5100 5000 P/N RS-232/RS-485 Interface b
NORTH AMERICA TDK-Lambda Americas Inc 405 Essex Rd. Neptune, NJ 07753 Tel: +1-732-922-9300 Fax: +1-732-922-1441 E-mail: sales@us.tdk-lambda.com www.us.tdk-lambda.com/hp UK TDK-Lambda UK Ltd. Kingsley Avenue Ilfracombe, Devon EX 34 8ES United Kingdom Tel: +44-1271-856666 Fax: +44-1271-864894 E-mail: powersolutions@emea.tdk-lambda.com www.uk.tdk-lambda.com FRANCE TDK-Lambda France SAS ZAC des Delaches BP 1077 - Gometz le Chatel 91940 LES ULIS Tel: +33 1 60 12 71 65 Fax: +33 1 60 12 71 66 E-mail: france@fr.