TECHNICAL MANUAL FOR GENESYSTM 750W/1500W Programmable DC Power Supplies Document: 83-507-013 Rev D TDK-Lambda Americas Inc. 405 Essex Road, Neptune, NJ 07753 Tel: (732) 922-9300 Fax: (732) 922-9334 Web: www.US.TDK-Lambda.
GENESYS™ Manual Supplement FOR UNITS EQUIPPED WITH “IEMD” OPTION, ALSO REFER TO MANUAL 83-030-200 IEMD. FOR UNITS EQUIPPED WITH “LAN” OPTION, REFER TO MANUAL 83-034-100. 83-507-013 Rev.
TABLE OF CONTENTS WARRANTY……………………………………………………………………………………………. SAFETY INSTRUCTIONS…………………………………………………………………………….. GERMAN SAFETY INSTRUCTIONS………………………………………………………………… Pg. 1 Pg. 2 Pg. 4 CHAPTER 1 GENERAL INFORMATION…………………………………………………………... 1.1 USER MANUAL CONTENT………………………………………………………………………. 1.2 INTRODUCTION…………………………………………………………………………………… 1.2.1 General description………………………………………………………………………….. 1.2.2 Models covered ……………………………………………………………………………... 1.2.3 Features and options ……………………………………………………………………….. 1.
TABLE OF CONTENTS 3.8.8 Address setting……………….…………………………………………………………….. 3.8.9 Baud rate setting……………………………………………………………………………. 3.9 CONNECTING THE LOAD……………………………………………………………………….. 3.9.1 Load Wiring………………………………………………………………………………….. 3.9.2 Current Carrying Capacity…………………………………………………………………. 3.9.3 Wire termination……………………………………………………………………………. 3.9.4 Noise and Impedance Effects……………………………………………………………... 3.9.5 Inductive loads………………………………………………………………………………. 3.9.6 Making the load connections……………………………………………………………….
TABLE OF CONTENTS 5.15.1 Basic parallel operation…………………………………………………………………… 5.15.2 Advanced parallel operation……………………………………………………………… 5.16 DAISY-CHAIN SHUT-OFF CONNECTION……………………………………………………. 5.17 FRONT PANEL LOCKING………………………………………………………………………. 5.17.1 Unlocked front panel……………………………………………………………………… 5.17.2 Locked front panel………………………………………………………………………… Pg. 41 Pg. 42 Pg. 45 Pg. 44 Pg. 44 Pg. 44 CHAPTER 6 REMOTE ANALOG PROGRAMMING……………………………………………… 6.1 INTRODUCTION…………………………………………………………………………………… 6.
TABLE OF CONTENTS 7.10.6 Status Control Commands……………………………………………………………….. 7.11 STATUS, ERROR AND SRQ REGISTERS………………………………………………….. 7.11.1 General Description……………………………………………………………………….. 7.11.2 Conditional Registers……………………………………………………………………… 7.11.3 Service Request: Enable and Event Registers…………………………………………. 7.12 SERIAL COMMUNICATION TEST SET-UP.…………………………………………………. Pg. 62 Pg. 62 Pg. 62 Pg. 63 Pg. 64 Pg. 67 CHAPTER 8 ISOLATED ANALOG PROGRAMMING OPTION………………………………… 8.
WARRANTY This TDK-Lambda Americas Inc. product is warranted against defects in materials and workmanship for a period of five years from date of shipment. During the warranty period, TDK-Lambda Americas Inc. will, at it’s option, either repair or replace products which prove to be defective. LIMITATION OF WARRANTY The warranty shall not apply to defects resulting from improper or inadequate usage or maintenance by the buyer, buyer supplied products or interfacing.
SAFETY INSTRUCTIONS CAUTION The following safety precautions must be observed during all phases of operation, service and repair of this equipment. Failure to comply with the safety precautions or warnings in this document violates safety standards of design, manufacture and intended use of this equipment and may impair the builtin protections within. TDK-Lambda Americas Inc. Inc. shall not be liable for user’s failure to comply with these requirements.
SAFETY INSTRUCTIONS ENVIRONMENTAL CONDITIONS The Genesys TM power supply series safety approval applies to the following operating conditions: *Indoor use *Maximum relative humidity: 90% (no condensation) *Pollution degree 2 *Ambient temperature: 0°C to 50°C *Altitude: up to 3000m CAUTION Risk of Electrical Shock Instruction manual symbol. The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual. Indicates hazardous voltage.
SICHERHEITS-INSTALLATIONS ANWEISUNGEN Vorsicht Vor Anschluss an das Netz ist die Aufstellanleitung wie nachstehend beschrieben zu beachten. Die nachstehenden Sicherheitsanweisugen mussen während aller Phasen des Betriebes, des Services und der Reparatur dieser Ausrustung beachtet werden. Alle notwendigen Bedingungen die sicherstellen, dass die Einrichtung zu keiner Gefahr im Sinne dieser Norm führen kann, sind in diesem Handbuch beschrieben. TDK-Lambda Americas Inc.
Anderungen and Bauteileersatz Ersatzteilaustausch – und Anderungen durfen nur von autorisiertem TDK-Lambda Americas Inc. SERVICE-PERSONEN durchgefuhrt werden. Fur Reparaturen oder Anderungen ist das Gerat zur TDK-Lambda Americas Inc. Service-Niederlassung zu retournieren. SICHERHEITS-HINWEISE Umweltbedingungen TM Die Genesys Stromversorgungs-Serie ist gemassden Sicherheitsabnahmen fur folgende Betriebsbedingungen zugelassen. *Stationare Einrichtungen in Gebauden. *Umgebungstemperaturebereich: 0-50°C.
CHAPTER 1 GENERAL INFORMATION 1.1 USER MANUAL CONTENT This User’s Manual contains the operating instructions, installation instructions and specifications of TM the Genesys 1500W and 750W power supply series. The instructions refer to the standard power supplies, including the built-in RS232/RS485 serial communication. For information related to operation with the optional IEEE programming, refer to User’s Manual for Power Supply Programming Interface. (TDK-Lambda Americas Inc. P/N 83-030-200) 1.
Remote sensing to compensate for voltage drop of power leads. External Analog Programming and Monitoring standard (0-5V or 0-10V, user selectable). Cooling fan speed control for low noise and extended fan life. Zero stacking-no ventilation holes at the top and bottom surface of the power supply. Optional GPIB interface (SCPI compatible). Optional Isolated Analog programming/monitoring (0-5V or 0-10V, user selectable and 4-20mA). 1.2.
1.2.9 Cooling and mechanical construction TM The Genesys series is cooled by internal fans. At the installation, care must be taken to allow free airflow into the power supply via the front panel and out of the power supply via the rear panel. The TM Genesys power supplies have a compact and lightweight package, which allows easy installation and space saving in the application equipment. CAUTION Observe all torque guidelines within this manual. Over-torquing may damage Unit or accessories.
CHAPTER 2 SPECIFICATIONS 2.1 OUTPUT RATING MODEL 1.Rated output voltage (*1) 2.Rated output current 750W (*2) 3.Rated output power 750W GEN V A W 6-100 6 100 600 8-90 8 90 720 12.5-60 12.5 60 750 20-38 20 38 760 30-25 30 25 750 40-19 40 19 760 – – – – MODEL 1.Rated output voltage (*1) 2.Rated Output Current 1500W (*2) 3.Rated output power 1500W GEN V A W 6-200 6 200 1200 8-180 8 180 1440 12.5-120 12.5 120 1500 20-76 20 76 1520 30-50 30 50 1500 40-38 40 38 1520 50-30 50 30 1500 2.
2.6 PROGRAMMING AND READBACK (RS232/485, Optional IEEE Interface) 1. Vout programming accuracy – 0.05% + 0.05% of rated output voltage. 2. Iout programming accuracy (*13) – 0.1% of actual output current + 0.1% of rated output current (for Iout >0.4% of rated Iout to 100% of rated Iout). 0.1% of actual output current +0.4% of rated output current (for Iout <0.4% of rated Iout to 0.4% of rated Iout). 3. Vout programming resolution. – 0.012% of full scale. 4. Iout programming resolution – 0.012% of full scale.
NOTES: *1: Minimum voltage is guaranteed to maximum 0.2% of the rated output voltage. *2: Minimum current is guaranteed to maximum 0.4% of the rated output current. *3: For cases where conformance to various safety standards (UL, IEC etc.) is required, to be described as 100-240Vac (50/60Hz). *4: At 100/200V input voltage and maximum output power. *5: From 85132Vac or 170265Vac, constant load. *6: From No-load to Full-load, constant input voltage. Measured at the sensing point in Remote Sense.
2.13 GENESYSTM 750W & 1500W POWER SUPPLIES OUTLINE DRAWINGS 12 83-507-013 Rev.
CHAPTER 3 INSTALLATION 3.1 GENERAL This Chapter contains instructions for initial inspection, preparation for use and repackaging for shipTM ment. Connection to PC, setting the communication port and linking Genesys power supplies are described in Chapter 7. 3.2 PREPARATION FOR USE NOTE Genesys power supplies generate magnetic fields which might affect the operation of other instruments. If your equipment is susceptible to magnetic fields, do not position it adjacent to the power supply.
3.4.2 Rack Mount Slides (optional): CAUTION Ensure that the screws used to attach the slides to the unit do not penetrate ore than 6mm into the sides of the unit. Use rack mount slides: General Devices P/N: CC3001-00-S160 or equivalent to install the unit in a standard 19” equipment rack. Refer to Fig. 3-1 for slides assembly instructions. Use three #10-320x0.38”(max.) screws at each side. To prevent internal damage, use the specified screw length only. Fig. 3-1: Rack-mount slides assembly 3.
WARNING Some components inside the power supply are at AC voltage even when the On/Off switch is in the “Off” position. To avoid electric shock hazard, disconnect the line cord and load and wait two minutes before removing cover. 3.7.1 AC Input Connector, 1500W models The AC input connector is a 3-Terminal wire clamp located on the rear panel. Use suitable wires and tightening torque as follows: 1. Wire diameter: 12AWG or 10AWG. 2. Tightening torque: 6.5 - 7.0 Lb-inch. 3.7.
4. Route the AC wires to the input connector terminals as required. To connect the wires, loosen the terminal screw, insert the stripped wire into the terminal and tighten the screw securely (4.4-5.3 Lb-inch). 5. Route the wires inside the cover to prevent pinching. Fasten the cover to the unit using the M3x8 Flat Head screws provided. Refer to Fig.3-3 for details. L N Cover M3x8 Flat Head screws (2 places) Assembled Strain Relief Fig.3-3: AC input cover and strain relief, 1500W models 3.
2. Connect the unit to an AC source as described in Section 3.7. 3. Connect a DVM with appropriate cables for the rated voltage to the output terminals. 4. Turn the front panel AC power switch to On. 3.8.3 Constant Voltage Check 1. Turn on the output by pressing the OUT pushbutton so the OUT LED illuminates. 2. Observe the power supply VOLT display and rotate the Voltage encoder. Ensure that the Output Voltage varies while the VOLT encoder is rotated.
3.8.7 Foldback Check WARNING Shorting the output may expose the user to hazardous voltages. Observe proper safety procedures. Refer to Section 5.5 for explanation of the FOLD function prior to performing the procedure below. 1. Ensure that the Output Voltage is set to approx. 10% of the unit rating. 2. Adjust the CURRENT encoder to set the Output Current setting to approx. 10% of the unit rating. 3. Momentarily press the FOLD button. Ensure that the FOLD LED illuminates.
2. Wire size should be selected to enable voltage drop per lead to be less than 1.0V at the rated current. Although units will compensate for up to 5V in each load wire, it is recommended to minimize the voltage drop (1V typical maximum) to prevent excessive output power consumption from the power supply and poor dynamic response to load changes. Please refer to Tables 3-2 and 3-3 for minimum wire length (to limit voltage drop) in American and European dimensions respectively.
3.9.4 Noise and Impedance Effects To minimize the noise pickup or radiation, the load wires and remote sense wires should be twisted pairs to the shortest possible length. Shielding of sense leads may be necessary in high noise environments. Where shielding is used, connect the shield to the chassis via a rear panel Ground screw. Even if noise is not a concern, the load and remote sense wires should be twisted-pairs to reduce coupling, which might impact the stability of power supply.
+V DC OUTPUT -V Wire terminal lug (2 places) M8x15 screw (2 places) Flat washer (2 places) Flat washer (2 places) Spring washer (2 places) Hex Nut (2 places) Screws tightening torque: 104-118 Lb-inch. Fig. 3-5: Load wires connection, 6V to 60V models +V DC OUTPUT -V Shield Fig. 3-6: bus-bars shield mounting 80V to 600V Models WARNING Hazardous voltages exist at the outputs and the load connections.
The 80V to 600V models have a four terminal wire clamp output connector. The two left terminals are the positive outputs and the two right terminals are the negative outputs. The connector requirements are as follows: 1. Wires: AWG18 to AWG10. 2. Tightening torque: 6.5-7.0 Lb-inch. Follow the instructions below for connection of the load wires to the power supply: 1. Strip approx. 10mm (0.39 inches) at the end of each of the wires. 2. Loosen the connector terminal screws. 3.
3.9.7 Connecting single loads, local sensing (default). Fig.3-10 shows recommended load and sensing connections for a single load. The local sense lines shown are default connections at the rear panel J2 sense connector. Local sensing is suitable for applications where load regulation is less critical. +V + Load Power Supply -V - Rem.sense -Local sense Load lines, twisted pair, shortest length possible. +Local sense + Rem.sense Fig.3-10: Single load connection, local sensing 3.9.
Load lines, twisted pair, shortest length possible. +V Power Supply + Load#1 -V + - Rem.sense -Local sense + +Local sense + Rem.sense Load#2 Load#3 Fig.3-12: Multiple loads connection, radial distribution, local sense 3.9.10 Multiple load connection with distribution terminals If remotely located output distribution terminals are used, the power supply output terminals should be connected to the distribution terminals by pair of twisted and/or shielded wires.
WARNING OUTPUT TERMINAL GROUNDING There is a potential shock hazard at the RS232/RS485 and the IEEE ports when using power supplies with rated or combined voltage greater than 400V with the Positive Output of the power supplies grounded. Do not connect the Positive output to ground when using the RS232/RS485 or IEEE under the above conditions. 3.10 LOCAL AND REMOTE SENSING The rear panel J2 sense connector is used to configure the power supply for local or remote sensing of the Output Voltage.
3.10.3 Remote sensing WARNING There is a potential shock hazard at the sense point when using a power supply with a rated Output Voltage greater than 40V. Ensure that the connections at the load end are shielded to prevent accidental contact with hazardous voltages. CAUTION When using shielded sense wires, ground the shield in one place only. The location can be the power supply chassis or one of the output terminals. Use remote sense where the load regulation at the load end is critical.
CHAPTER 4 FRONT AND REAR PANEL CONTROLS AND CONNECTORS 4.1 INTRODUCTION TM The Genesys Power Supply series has a full set of controls, indicators and connectors that allow the user to easily setup and operate the unit. Before starting to operate the unit, please read the following Sections for explanation of the functions of the controls and connectors terminals. -Section 4.2: Front Panel Controls and Indicators. -Section 4.3: Rear Panel Connections and Controls. 4.
Table 4-1: Front Panel Controls and Indicators Number Control/Indicator 4 CURRENT display 5 CURRENT indicator 6 CURRENT control 7 OUT button 8 OUT indicator 9 REM/LOC button 10 REM/LOC indicator 11 FOLD button 12 FOLD indicator 13 OVP/UVL button Description 4 digit, 7 segment LED display. Normally displays the Output Current. When the PREV button is pressed, the display indicates the programmed setting of Output Current.
14 Main function: Press PREV to display the Output Voltage and Current setting. For 5 sec. the display will show the setting and then it will return to show the actual Output Voltage and Current. Auxiliary function: Front Panel Lock. Press and hold PREV button to toggle between “Locked front panel” and “Unlocked front panel”. The display will cycle between “LFP” and “UFP”. Releasing the PREV button while one of the modes is displayed selects that mode.
Table 4-2: Rear panel connections and controls Number Item 1 AC input connector 2 DC output 3 Remote-In connector 4 Remote Out connector 5 J1 Analog Remote connector 6 SW1 Setup switch 7 J2 Remote sense connector Blank Sub-plate 8 9 IEEE switch 10 Ground screw Description Wire clamp connector for 1500W units. IEC connector for 750W units. Section Bus-bars for 6V to 60V models. Wire clamp connector for 80V to 600V models.
1 2 3 4 5 6 7 8 9 Fig.4-3: SW1 setup DIP-switch 4.4.1 SW1 position function Refer to Table 4-3 for description of SW1 position functions. The factory default setting is Down for all positions.
4.5 REAR PANEL J1 PROGRAMMING AND MONITORNG CONNECTOR The J1 Programming and Monitoring connector is a DB25 subminiature connector located on the power supply rear panel. Refer to Table 4-4 for description of the connector functions. The power supply default configuration is Local operation, which does not require connections to J1. For remote operation using J1 signals, use the plug provided with power supply (or equivalent type).
Same ground as P/S negative sense (-S) VMON COM CV/CC IF_COM IF_COM ENA_IN IPGM VPGM LOC/ REM 13 25 P IMON IPGM_RTN VPGM_RTN LOC/REM SIGNAL 12 24 11 23 10 22 9 8 21 6 7 20 19 5 18 17 4 2 3 16 15 1 14 Isolated from PS outputs, same ground as RS232/RS485 ENA_OUT SO PS_OK Fig.
CHAPTER 5 LOCAL OPERATION 5.1 INTRODUCTION This Chapter describes the operating modes that are not involved in programming and monitoring the power supply via its serial communication port (RS232/RS485) or by remote analog signals. Ensure that the REM/LOC LED on the front panel is Off, indicating Local mode. If the REM/LOC LED is On, press the front panel REM/LOC button to change the operating mode to Local. -For information regarding Remote Analog Programming, refer to Chapter 6.
-Enabled output, power supply in Constant Voltage mode: Press the PREV button and then rotate the CURRENT encoder knob. The CURRENT meter will show the programmed Output Current for 5 seconds after the adjustment has been completed, and then will return to show the actual load current. -Enabled output, power supply in Constant Current mode: Rotate the CURRENT encoder knob to adjust the Output Current. 4. Adjustment resolution can be set to Coarse or Fine adjustment.
5.4 UNDER VOLTAGE LIMIT (UVL) The UVL prevents adjustment of the Output Voltage below a certain limit. The combination of UVL and OVP functions, allow the user to create a protection window for sensitive load circuitry. 5.4.1 Setting the UVL level Setting the UVL can be made when the power supply output is Enabled (On) or Disabled (Off). To set the UVL level, press the OVP/UVL button TWICE, so that the CURRENT meter shows “UUL”. The VOLTAGE meter shows the UVL setting level.
AC power; even if SO is at an Off level). After an On to Off transition it is detected, the SO will Enable or Disable the power supply output according to the signal level or the short/open applied to J1. This function is useful for connecting power supplies in a “Daisy-chain” (refer to Section 5.16). The SO control can also be used to reset the OVP and Fold Protection (refer to Section 5.3 and 5.5 for details).
low, with a maximum sink current of 1mA; when no fault condition occurs, the PS_OK level is high with a maximum source current of 2mA. The following faults will set the PS_OK to a Fault state: *OTP *Enable/Disable open (Power supply is disabled) *OVP *SO (Rear panel Shut-Off, Power Supply is shut off) *Foldback *IEEE failure (With optional IEEE interface) *AC fail *Output Off 5.
5.14 SERIES OPERATION Power supplies of the SAME MODEL can be connected in series to obtain increased output voltage. Split connection of the power supplies gives positive and negative output voltage. CAUTION Do not connected power supplies from different manufacturers in series or in parallel. 5.14.1 Series connection for increased output voltage In this mode, two units are connected so that their outputs are summed.
3. Programming by external resistor: 4. Programming via the Serial Communication port (RS232/RS485): Programming by external resistor is possible. Refer to Section 6-5 for details. The communication port is referenced to the IF_COM which is isolated from the power supply output potential. Therefore power supplies connected in series can be daisy-chained using the Remote-In and Remote-Out connectors. Refer to Chapter 7 for details. 5.14.
5.15 PARALLEL OPERATION Up to four units of the same VOLTAGE and CURRENT rating can be connected in parallel to provide up to four times the Output Current capability. One of the units operates as a Master and the remaining units are Slaves. The Slave units are analog programmed by the Master unit. In remote digital operation, only the Master unit can be programmed by the computer, while the Slave units may be connected to the computer for voltage, current and status readback only.
6. Connection to the load In parallel operation, power supplies can be connected in local or remote sensing. Refer to Fig. 54 and 5-5 for typical connections of parallel power supplies. The figures show the connection of two units, however the same connection method applies for up to 4 units. 5.15.2 Advanced parallel operation In this method, multiple supplies can be configured to parallel operation as a single power supply.
c) The Master and Slave modes are stored in the power supply EEPROM when the AC power is turned off. The system will return to the Master/Slave mode upon re-application of AC power. 4. CURRENT display accuracy In the advanced parallel mode, the Master unit calculates the total current by multiplying the Master output current by the number of Slave units. In this method, the CURRENT display accuracy is 2% +/- 1 count.
+S To J1-10 SLAVE#2 POWER SUPPLY -S -S Twisted pair +S MASTER POWER SUPPLY +V As short as possible -V Twisted pair +S J1-25 P IPGM J1-8 J1-12 J1-10 LOAD +V SLAVE#1 POWER SUPPLY -S -LS -S -V +LS +S Fig.5-5: Parallel operation with Remote sensing 5.16 DAISY-CHAIN CONNECTION It is possible to configure a multiple power supply system to shut down all the units when a fault condition occurs in one of the units.
CHAPTER 6 REMOTE ANALOG PROGRAMMING 6.1 INTRODUCTION The rear panel connector J1 allows the user to program the power supply Output Voltage and Current with an analog device. J1 also provides monitoring signals for Output Voltage and Output Current. The programming range and monitoring signals range can be selected between 0-5V or 0-10V using the setup switch SW1.
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND OUTPUT CURRENT CAUTION To maintain the power supply isolation and to prevent ground loops, use an isolated programming source when operating the power supply via remote analog programming at the J1 connector. Perform the following procedure to set the power supply to Remote Voltage programming: 1. Turn the power supply AC On/Off switch to Off. 2. Set setup switch SW1, positions 1 and 2 to their UP position. 3.
6.5 RESISITIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT For resistive programming, internal current sources, for Output Voltage and/or Output Current control, supply 1mA current through external programming resistors connected between J1-9 & 22 and J1-10 & 23. The voltage across the programming resistors is used as a programming voltage for the power supply. Resistance of 05Kohm or 010Kohm can be selected to program the Output Voltage and Output Current from zero to full scale.
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT The J1 connector, located on the rear panel provides analog signals for monitoring the Output Voltage and Output Current. Selection of the voltage range between 0-5V or 0-10V is made by setup switch SW1-4. The monitoring signals represent 0 to 100% of the power supply Output Voltage and Output Current. The monitor outputs have 500 ohm series output resistance.
CHAPTER 7 RS232 & RS485 REMOTE CONTROL 7.1 INTRODUCTION TM This Chapter describes the operation of the Genesys 3300W power supplies via the serial communication port. Details of the initial set-up, operation via RS232 or RS485, the command set and the communication protocol are described in this Chapter. 7.2 CONFIGURATION 7.2.
2. There are two Remote modes: 1. Remote: In this mode, return to local can be made by the front panel REM/LOC or via serial port command RMT 0. Set the unit into Remote mode via serial port RMT 1 command. 2. Local Lockout: In this mode the unit can be returned to Remote mode via the serial port RMT 1 command or by turning off the AC power until the display turns off, and then turn it to on again. In local Lockout mode, the front panel REM/LOC button is not active.
7.4 MD MODE OPTION (Factory Installed) 7.4.1 MD Mode Description The GEN supply is capable of operating in a multi drop environment - more than 1 supply conducting serial communications on a single serial bus. A maximum of 31 GEN supplies can operate in this single bus. Upon power up the Gen will enter the point-to-point mode in which it is assumed that only 1 supply will operate on a serial bus. MD Mode must be enabled - Ref. Section 7.10.2.2. The user must set all Slave supplies to a unique address.
7.5 CONNECTING POWER SUPPLIES TO RS232 OR RS485 BUS 7.5.1 Single power supply 1. Select the desired interface RS232 or RS485 using rear panel setup switch SW1-6 (Section 4-4). -RS232: DOWN position -RS485: UP position 2. Connect rear panel IN connector to the controller RS232 or RS485 port using a suitable shielded cable. Refer to Figures 7-2, 7-3 and 7-4 for available RS232 and RS485 cables. L=2m typ. 13 8 1 1 Sockets DB-25 CONNECTOR PIN NO. 1 2 3 7 NAME SHIELD TX RX SG 8 PIN CONNECTOR PIN NO.
7.5.2 Multi power supply connection to RS232 or RS485 bus Up to 31 units can be connected (daisy chained) to the RS232 or RS485 bus. The first unit connects to the controller via RS232 or RS485 and the other units are connected via the RS485 bus. 1. First unit connection: Refer to Section 7.5.1 for connecting the first unit to the controller. 2. Other units connection: The other units on the bus are connected via their RS485 interface. Refer to Figure 7-5 for typical connection.
7.6.7 Error message If an error is detected in command or query, the power supply will respond with an error message. Refer to Section 7.7 for details. 7.6.8 Backspace The backspace character (ASCII 8) clears the last character sent to the power supply. 7.7 ERROR MESSAGES The power supply will return error messages for illegal commands and illegal programming parameters. Refer to Table 7-1 for programming error messages and Table 7-2 for command error messages.
7.8.3 # 1 4 Initialization Control Commands Command Description ADR is followed by address, which can be 0 to 30 and is used to access the ADR n power supply. Clear status. Sets FEVE and SEVE registers to zero (refer to Section 7-11). CLS Reset command.
# Command 7 DVC? 9 FILTER nn FILTER? 10 OUT n 11 OUT? 12 FLD n 13 FLD? 14 FBD nn 15 16 FBD ? FBDRST 17 OVP n 18 OVP? 19 OVM 20 UVL n 21 UVL? 22 AST n 23 AST? 24 SAV 25 RCL 8 Description Display Voltage and Current data. Data will be returned as a string of ASCII characters. A comma will separate the different fields. The fields, in order, are: Measured Voltage, Programmed Voltage, Measured Current, Programmed Current, Over Voltage Set Point and Under Voltage Set Point.
26 MODE? 27 MS? Returns the power supply operation mode. When the power supply is On (OUT 1) it will return “CV” or “CC”. When the power supply is OFF (OUT 0 or fault shutdown) it will return “OFF”. Returns the Master/Slave setting. Master: n= 1, 2, 3, or 4 Slave: n=0 NOTES: 1. In Advanced parallel mode (refer to Sec. 5.15.2), “n” is the total system current. 2. In Advanced parallel mode, “MC?” returns the Master unit current multiplied by the number of slave units +1. 7.9 GLOBAL OUTPUT COMMANDS 7.9.
7.10 SINGLE BYTE COMMANDS 7.10.1 General Single byte commands are commands in which all the necessary data for the supply to act upon is contained in a single byte. Single byte commands will be executed immediately by the supply. If the command requires data to be sent to the HOST PC or IEEE Board (see sections 7.10.4 and 7.10.3.1) that response will be transmitted immediately with no delay due to any software overhead. With the exception of the Disconnect from communications command, section 7.10.3.
7.10.4 Addressed commands with response 7.10.4.1 Read registers Send (0x80 + Address) (1 byte binary - send 2 times sequentially). The supply will return the contents of the Status Condition Register, the Status Enable Register, the Status Event Register (SEVE?), the Fault Condition Register, the Fault Enable Register and the Fault Event Register IFEVE/). All registers will be represented in two Hex bytes.
Table 7-3.
GEN750W models Table 7-4: Current programming range GEN1500W models Table 7-5: Current programming range Minimum (A) Maximum (A) GEN6-100 000.00 100.00 GEN6-200 000.00 200.00 GEN8-90 00.00 90.00 GEN8-180 000.00 180.00 GEN12.5-60 00.000 60.000 GEN12.5-120 000.00 120.00 GEN20-38 00.000 38.000 GEN20-76 00.00 76.00 GEN30-25 00.000 25.000 GEN30-50 00.000 50.000 GEN40-19 00.000 19.000 GEN40-38 00.000 38.000 GEN60-12.5 00.000 12.500 GEN60-25 00.000 25.000 GEN80-9.5 0.
7.10.6 Status Control Commands Refer to Section 7-8 for definition of the registers. # Command 1 STT? 2 3 4 5 6 7 8 9 FLT? FENA FENA? FEVE? STAT? SENA SENA? SEVE? Description Reads the complete power supply status. Returns ASCII characters representing the following data, separated by commas: MV PC PV SR MC FR Example response: MV(45.
Command Error (”Cnn”) One response for every command or query received. Response messages Execution Error (”Enn”) Query Response (”message”) Command Response (”OK”) Status Registers Condition Constant Voltage Constant Current No Fault Fault Auto Start Fold Enabled Spare Local Mode LSB 0 1 2 3 4 CV CC NFLT FLT AST 5 FDE 6 0 MSB 7 LCL Enable 0 0 0 Serial TXD Event CV CC NFLT FLT 0 0 0 LCL “Inn” and CR SRQ Messages One SRQ when SEVE goes from all zeroes to any bit set.
7.11.2 Conditional Registers (continued) Table 7-8: Fault Condition Register BIT Fault name Fault symbol Spare bit SPARE Fixed to zero Fixed to zero 1 AC Fail AC AC fail has occurred. The AC input returns to normal. 2 Over temperature OTP OTP shutdown has occurred. The power supply cools down. 3 Foldback FOLD 4 Over voltage OVP 5 Shut Off SO The supply output is turned On by front panel button or OUT 1 command. The supply output is turned ON by front panel button or OUT 1 command.
Refer to Tables 7-10 to 7-13 for details of the Enable and Event registers. 1. Fault Enable Register The Fault Enable Register is set to the enable faults SRQs.
3. Status Enable Register The Status Enable Register is set by the user to Enable SRQs for changes in power supply status. Table 7-12: Status Enable Register BIT Status name Status symbol Bit Set condition Bit reset condition User command: “SENA nn” is received, where nn is User command: hexadecimal bits. “SENA nn” is If “nn”=00, no SRQ is sent received, where nn is hexadecimal when there is a change in Status Condition Register. bits.
7.12 SERIAL COMMUNICATION TEST SET-UP Use the following instructions as basic set-up to test the serial communication operation. TM 1.Equipment: PC with Windows Hyper Terminal, software installed, Genesys Power supply, RS232 cable. 2. PC set-up: 2.1 Open Hyper Terminal…………………….New Connection. 2.2 Enter a name 2.3 Connect to…………………………………Direct to Com 1 or Com 2 2.4 Configure port properties: Bits per second……9600 Data bits……………8 Parity……………….None Stop bits……………1 Flow control……….None 2.
CHAPTER 8 ISOLATED ANALOG PROGRAMMING OPTION 8.1 INTRODUCTION TM Isolated Analog Programming is an internal Option Card for analog programming of the Genesys power supply series. The option is factory installed and cannot be obtained with a GPIB (IEEE-488) Interface. Output Voltage and Output Current can be programmed and readback through optically isolated signals which are isolated from all other ground references in the power supply. There are two types of Isolated Analog programming cards: 1.
8.3 ISOLATED PROGRAMMING & MONITORING CONNECTOR Refer to Table 8-1 for detailed description of the rear panel Isolated Programming & Monitoring connector. To provide the lowest noise performance, it is recommended to use shielded-twisted pair wiring. Refer to Fig.8-1 for description of the Isolated Analog Programming & Monitoring connector. Isolated programming plug P/N: MC1.5/8-ST-3.81, Phoenix. 1 2 3 5 4 6 7 8 Shield Shield +VPROG_ISO +IPROG_ISO GND_ISO +IMON_ISO +VMON_ISO GND_ISO Fig.
8.4 SETUP AND OPERATING INSTRUCTIONS CAUTION To prevent damage to the unit, do not program the output voltage and current to higher than the power supply rating. 8.4.1 Setting up the power supply for 0-5V/0-10V Isolated Programming and Monitoring Perform the following procedure to configure the power supply: 1. Turn the power supply AC power switch to Off. 2. Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4). 3. Set the Setup switch SW1, positions 1 and 2 to the UP position. 4.
CHAPTER 9 MAINTENANCE 9.1 INTRODUCTION This Chapter provides information about maintenance, calibration and troubleshooting. 9.2 UNITS UNDER WARRANTY Units requiring repair during the warranty period should be returned to a TDK-Lambda Americas Inc. authorized service facility. Refer to the addresses listing on the back cover of this User’s Manual. Unauthorized repairs performed by other than the authorized service facilities may void the warranty. 9.
SYMPTOM Output Voltage will not adjust. Front panel CC LED is On. Output Voltage will not adjust Front panel CV Led is On. Output Current will not adjust. Front panel CV LED is on. Large ripple present in output. CHECK Is the unit in constant current mode? Check if output voltage is adjusted above OVP setting or below UVL setting. Is the unit in constant voltage mode? Is the power supply in remote sense? Is the voltage drop on the load wire high? No output.