General Specifications Genesys™ 750W/1500W
Outline Drawing Genesys™ 750W/1500W Units
NOTE
1. PLUG CONNECTORS INCLUDED WITH THE POWER SUPPLY
2. CHASSIS SLIDES MOUNTING HOLES #10-32 MARKED "A"
GENERAL DEVICES P/N: CC301-00-S160 OR EQUIVALENT
*1: For cases where conformance to various safety standards (UL, IEC etc.) is required, to be described as 100-240Vac (50/60Hz).
2.1 INPUT CHARACTERISTICS
1. Input voltage/freq. (*1)
2. Power Factor 0.99 @100/200Vac, rated output power.
3. EN61000-3-2,3 compliance Complies with EN61000-3-2 class A and EN61000-3-3 at 20~100% output power.
4. Input current 100/200Vac
5. Inrush current 100/200Vac 750W :Less than 25A, 1500W :Less than 50A
6. Hold-up time
More than 20mS , 100Vac , at 100% load.
750W :10.5A / 5A, 1500W :21A / 11A
85~265Vac continuous, 47~63Hz, single phase
2.6 MECHANICAL CONSTRUCTION
1. Cooling
2. Dimensions (WxHxD) W: 16.64in, H: 1.72in, D: 17.04in (excluding connectors, encoders, handles, etc.)
3. Weight
750W: 7Kg (15 Lbs) 1500W: 8.5Kg (18 Lbs)
4. AC Input connector 750W: IEC320 AC Inlet.
1500W: Screw terminal block, Phoenix P/N: FRONT-4-H-7.62 , with strain relief
5.Output connectors
6V to 60V models: Bus-bars (hole Ø 8.5mm). 80V to 600V models: Terminal block, Phoenix P/N: FRONT-4-H-7.62
Forced air flow: from front to rear. No ventilation holes at the top or bottom of the chassis; Variable fan speed.
2.7 RELIABILITY SPECS
1. Warranty 5 years.
1. Parallel Operation
2. Series Operation
Up to 4 identical units in master/slave mode with parallel current summing (Advanced Parallel)
Up to 2 units. with external diodes. 600V Max to Chassis ground
2.2 POWER SUPPLY CONFIGURATION
2.3 ENVIRONMENTAL CONDITIONS
1. Operating temp
2. Storage temp
-20~70 °C
3. Operating humidity
30~90% RH (non-condensing).
4. Storage humidity
10~95% RH (non-condensing).
5. Vibration
MIL-810E, method 514.4 , test cond. I-3.3.1. The EUT is fixed to the vibrating surface.
6. Shock
Less than 20G , half sine , 11mSec. Unit is unpacked.
7. Altitude
Operating: 10000ft (3000m) , Non operating: 40000ft (12000m).
0~50 °C, 100% load.
EN55022A, FCC part 15-A, VCCI-1.
2.4 EMC
1.Applicable Standards:
2.ESD
IEC1000-4-2. Air-disch.-8KV, contact disch.-4KV
3.Fast transients IEC1000-4-4. 2KV
4.Surge immunity IEC1000-4-5. 1KV line to line, 2KV line to ground
5.Conducted immunity
IEC1000-4-6, 3V
6.Radiated immunity IEC1000-4-3, 3V/m
7.Conducted emission EN55022B,FCC part 15J-B,VCCI-2
8.Radiated emission
EN55022A,FCC part 15-A,VCCI-1
9.Voltage dips EN61000-4-11
10. Conducted emission
11. Radiated emission
EN55022B, FCC part 15-B, VCCI-2.
More than 100Mohm at 25 C , 70% RH, 500Vdc
2.5 SAFETY
1.Applicable standards:
400<Vout<600V:Output is hazardous, IEEE/Isolated analog are not SELV.
2.Withstand voltage
60<Vout<600V models: Input-Haz. Output: 2.5KVrms 1min, Input-SELV: 3KVrms 1min.
Hazardous Output.-SELV: 1.9KVrms 1min, Hazardous Output-Ground:1.9KVrms 1min.
3.Insulation resistance
CE Mark, UL60950,EN60950 listed. Vout<60V:Output is SELV , IEEE/Isolated analog are SELV.
60<Vout<400V: Output is hazardous, IEEE/Isolated analog are SELV.
Vout<60V models :Input-Outputs (SELV): 3.0KVrms 1min, Input-Ground: 2.0KVrms 1min.
Input-Ground: 2KVrms 1min.