Information


2.7 INSTRUMENT SELECT COMMANDS
2.7.1 SELECT SUPPLY
Commands Interface to conduct communications with a designated supply when in
Multi Drop Mode.
Syntax:
INSTrument:NSELect<SP><nn> where nn is the address of the select-
ed supply
Example:
INSTRUMENT:SELECT 17
Notes:
Upon power up the Master Supply will be automatically selected.
:NSELect may be replaced with :SELect
2.7.2 READ SELECTED SUPPLY NUMBER
Syntax:
INSTrument:NSELect?
Notes:
Returns the selected .Supply number ’xx’
2.8 STATUS COMMANDS
2.8.1 READ OPERATIONAL CONDITION ‘EVENT’ REGISTER COMMAND
Reads the Operational Condition Event Register and puts the result in the Output Queue.
Syntax:
STATus:OPERation[:EVENt]?
Alternate Format:
STATUS:OPERATION?
Example:
STATUS:OPERATION:EVENT?
Notes:
The returned <value> is a decimal number representing the sum of all the event bits.
The range of <value> is 0 to 255.
2.8.2 READ OPERATIONAL CONDITION ‘CONDITION’ REGISTER COMMAND
Reads the Operational Condition Register and puts the result in the Output Queue.
Syntax:
STATus:OPERation:CONDition?
Example:
STATUS:OPERATION:CONDITION?
Notes: