Datasheet

DRL10-100 Series
10-100W Low Prole
DIN Rail Mount Power Supplies
DRL10-100 Series
1
www.emea.tdk-lambda.com/drl
,QGXVWULDO
7HVW
$XWRPDWLRQ
Features Benets
•HighEfciency,upto90%@230VAC •EnergySaving-ImprovedThermalPerformance
•UL1310Class2Compliant •ReducedInstallationCosts(NECClass2)
 •LowNoLoadConsumption •ErPCompliant
•LongE-Cap-Life(>8years@40°C,75%Load,230VAC) •HighIn-ServiceLifetime
 •ClassII,WideRangeInput(85-264VAC) •GlobalApplication,NoEarthRequired
Specication
Model DRL10 DRL30 DRL60 DRL100
InputVoltageRange V 85-264VAC(Withstands300VACfor5seconds)
InputFrequency Hz 47-63Hz
InrushCurrentat230VAC
(typ)(ColdStart)
A 40 50 60 60
PowerFactor(115/230VAC) MeetsIEC61000-3-2ClassA
InputCurrent(110/230VAC)
0.56/0.42 0.58/0.45 0.5/0.43 0.5/0.47
A
0.18/0.12 0.6/0.4 1.2/0.8 2.0/1.1
Line&LoadRegulation - Seemodelselector
Ripple&Noise - 12V&15V:120mv,24V:240mv
OvercurrentProtection - >105%Hiccupwithautorecovery
OvervoltageProtection - Seemodelselector.CycleACinputvoltagetoreset
HoldUpTime(typ)at115VACInput ms 20 20 20 15
Efciency - Seemodelselector
NoLoadPowerDraw W <0.3 <0.3 <0.5 <0.5
LEDIndicator - GreenLEDindicatesDCisOK
DRL10,30,60:-20°to+71°,deratelinearlyfrom100%to60%loadfrom55°to71°
OperatingTemperature(-25°Cstart-up) °C DRL100:-20°to+71°,deratelinearlyfrom100%to60%loadfrom51°to71°
DRL100(<115VAC):-20°to+71°,deratelinearlyfrom100%to40%loadfrom40°to71°
StorageTemperature °C 40°to+85°
OperatingHumidity(noncondensing) %RH 5-95
ParallelOperation - Notavailable
SeriesOpereration - Possible
Cooling - Convection
OperatingAltitude m 3,000
WithstandVoltage(For1minute) VAC InputtoOutput3kVAC
IsolationResistance MΩ >100MΩat25°C,70%RH&500VDC
Vibration(Operating) -
IEC60068-2-6,SineWave,10-500Hz,19.6m/s
2
(2Gpeak)
10minpercycle,60minforallX,Y,Zdirections
Shock -
IEC60068-2-27,HalfSineWave,39.2m/s
2
(4G)foradurationof22ms
3shocksforeach3directions,9timesintotal
SafetyAgencyCertications
- UL508Listed,UL60950-1,UL1310Class2(LPS),NECClass2(see model selector table),
CSA22.2No.60950-1,EN60950-1,CEMark
Conducted&RadiatedEMI - EN55022-BConducted,EN55022-ARadiated
Immunity - EN61000-4-2(lvl3),-3(lvl3),-4(lvl4),-5(lvl3),-6(lvl3),-8(lvl4),-11(class3)
LineDip(200-240VAC) - SEMIF47Compliant
Weight(Typ) g 65 120 200 280
Size(WxHxD) mm 18x91x55.6 36x91x55.6 54x91x55.6 72x91x55.6
CaseMaterial - FlameRetardantPolycarbonate(UL94V-0)
Warranty yrs 3