Datasheet

11-800-526-2324 • www.us.tdk-lambda.com/lp/
DLP-PU Series
Features
u OR-ing Diodes Included
u Alarm Signals
u LED Indicators
u DIN Rail Mounting
u Can connect two units in parallel
u Output voltage monitoring (via relays)
Power Supply Parallel or Redundancy Module
Note: See Installation Manual for full details, test methods of parameters and application notes
Model DLP-PU/E
Input Voltage Range VDC 21 - 28VDC
Number of inputs - Two
Maximum Input Current A 20A per input
Maximum Output Current A 20A
Overcurrent protection - None
Voltage Drop VDC 0.5V
Maximum Reverse Voltage VDC 35VDC
LED Indicators - Two green LEDs indicating each input is “good”
Input Voltage Alarm - Relay off when input is <19.2V (±1%) or > 30V (±5%). NO and NC contacts
Relay contact rating (max) - 28VDC, 1A or 120VAC, 0.5A (5mA minimum recommended)
Cooling - Convection
Operating Temperature -10 to +70°C, derate linearly to 60% from 60 to 70°C
Storage Temperature - -30 to +90°C
Humidity - Operating: 30 - 90%RH, Storage: 10 - 95%RH (non condensing)
Withstand Voltage - Input or Output - Chassis, Input or Output - Relay Contacts,
Relay Contacts to Chassis; 500VAC for 1 min.
Isolation Resistance - Input or Output - Chassis, Input or Output - Relay Contacts,
Relay Contacts to Chassis; >10M Ohms at 25°C, 70%RH and 500VDC
Vibration - Non operating, mounted on DIN Rail,10-55Hz (sweep for 1 min),
9.8m/s
2
constant X, Y, Z each for 1 hour
Shock - 196m/s
2
Safety Agency Approval - UL60950-1, CSA60950-1, EN60950-1, UL508, CSA22.2 No.14, EN60529 IP20, EN50178 Cat 1
Size mm/in 50 x 97 x 110mm, 1.97x 3.81 x 4.33”
Weight g 470g
Warranty yrs Three Years
Specifi cations
Key Market Segments & Applications