Datasheet
11-800-526-2324 • www.us.tdk-lambda.com/lp/
DLP-PU Series
Features
u OR-ing Diodes Included
u Alarm Signals
u LED Indicators
u DIN Rail Mounting
u Can connect two units in parallel
u Output voltage monitoring (via relays)
Power Supply Parallel or Redundancy Module
Note: See Installation Manual for full details, test methods of parameters and application notes
  Model    DLP-PU/E           
  Input Voltage Range  VDC  21 - 28VDC
  Number of inputs  -  Two
  Maximum Input Current  A  20A per input
  Maximum Output Current  A  20A
  Overcurrent protection  -  None
  Voltage Drop  VDC  0.5V
  Maximum Reverse Voltage  VDC  35VDC
  LED Indicators  -  Two green LEDs indicating each input is “good”
  Input Voltage Alarm  -  Relay off when input is <19.2V (±1%) or > 30V (±5%). NO and NC contacts
  Relay contact rating (max)  -  28VDC, 1A or 120VAC, 0.5A (5mA minimum recommended)
  Cooling  -  Convection
  Operating Temperature    -10 to +70°C, derate linearly to 60% from 60 to 70°C
  Storage Temperature  -  -30 to +90°C
  Humidity  -  Operating: 30 - 90%RH, Storage: 10 - 95%RH (non condensing)
  Withstand Voltage  -  Input or Output - Chassis, Input or Output - Relay Contacts, 
      Relay Contacts to Chassis; 500VAC for 1 min.
  Isolation Resistance  -  Input or Output - Chassis, Input or Output - Relay Contacts, 
      Relay Contacts to Chassis; >10M Ohms at 25°C, 70%RH and 500VDC
  Vibration  -  Non operating, mounted on DIN Rail,10-55Hz (sweep for 1 min), 
      9.8m/s
2
 constant X, Y, Z each for 1 hour
  Shock  -  196m/s
2
  Safety Agency Approval  -  UL60950-1, CSA60950-1, EN60950-1, UL508, CSA22.2 No.14, EN60529 IP20, EN50178 Cat 1
  Size  mm/in  50 x 97 x 110mm, 1.97x 3.81 x 4.33”
  Weight  g  470g
  Warranty  yrs  Three Years
Specifi cations
Key Market Segments & Applications