Datasheet

CUS200M Series
3
Output Derating according to the Mounting Direction
42
4-11. Standby Power
A fixed 5V standby power is provided through STBY+ and STBY- of CN61. And its maximum output current is 0.6A at
convection cooling and 1A at forced air cooling. For CUS200M standard model, STBY- and V- are shorted together
internally. If you want an insulated standby mode power, please contact TDK-Lambda Corporation.
4-12. DC_OK Signal
DC_OK signal shows “High” level (4.5V~5V) to indicate power supply operating normal, and can source maximum 2mA
current.
When power supp
ly stops operating, the signal will turn to “Low” level (0V~0.5V), and the maximum sink current is 1mA.
4-13. Remote ON/OFF Control
R- is for remote ON/OFF control function. Usually, a switch (relay, transistor etc.) is connected between R- and STBY-
for remote ON/OFF control. Close the switch can shut down the main output without turning off the AC input. For
CUS200M standard model, R+ is connected to STBY+ internally, not for customer using. If you have special
requirem
ent about remote ON/OFF control ( e.g. reverse control logic, insulation control etc.), please contact
TDK-Lambda Corporation.
STBY+
STBY-
R+
R-
Switch
5. Mounting Directions
5-1. Output Derating according to the Mounting Direction
Recommended standard mounting direction is (A). Mounting direction (B)-(E) are also possible. Refer to the output
derating below.
Load (%) of derating curve indicates output power.
Output Derating CUS200M-18, CUS200M-24, CUS200M-48
43
5-2. Output Derating
Make sure that the specified temperature range is maintained.
Convection cooling
MODEL: CUS200M-18, CUS200M-24, CUS200M-48
Ta (°C)
MOUNTING A,B MOUNTING C,D MOUNTING E (NOTE1)
LOAD (%) LOAD (%) LOAD (%)
-20 - +40 100 100 100
50 100 80 100
60 75 60 75
65 63 50 -
70 50 40 -
MODEL: CUS200M-12
Ta (°C)
MOUNTING A,B MOUNTING C,D MOUNTING E (NOTE1)
LOAD (%) LOAD (%) LOAD (%)
-20 - +40 100 100 100
50 100 80 80
60 75 60 60
65 63 50 -
70 50 40 -
Output Derating CUS200M-12
43
5-2. Output Derating
Make sure that the specified temperature range is maintained.
Convection cooling
MODEL: CUS200M-18, CUS200M-24, CUS200M-48
Ta (°C)
MOUNTING A,B MOUNTING C,D MOUNTING E (NOTE1)
LOAD (%) LOAD (%) LOAD (%)
-20 - +40 100 100 100
50 100 80 100
60 75 60 75
65 63 50 -
70 50 40 -
MODEL: CUS200M-12
Ta (°C)
MOUNTING A,B MOUNTING C,D MOUNTING E (NOTE1)
LOAD (%) LOAD (%) LOAD (%)
-20 - +40 100 100 100
50 100 80 80
60 75 60 60
65 63 50 -
70 50 40 -