KIT PACKAGE OPTION (KP)
KIT PACKAGE OPTION HG7 I, O, & M Manual
46
Product Technical Specifications
Table 9 lists the major technical specifications and intended environments for the HG7 Harmonic Filter
components.
Table 9 HG7 “KP” Option Harmonic Filter Components Technical Specifications
Voltage ratings 240, 480 and 600 V, 3 ph, 60 Hz
380 415 V, 3 ph, 50 Hz
kVar ratings 3 to 270 kVar depending on voltage.
Load types 3-phase diode bridge rectifier loads such as PWM AC drives
Load power range 7.5 -900 Hp depending on voltage, 4710kW
Series Reactor Current
ratings
The included series reactors can tolerate 200% of rated current for at
least 3 minutes.
Maximum elevation for all
components
3,000 feet (1,000 meters) as standard. Product must be equipped with
special cooling provisions for operation above this altitude.
Maximum ambient operating
temperature
50°C (122°F) Open Panel; 40°C (104°F) Enclosed Panel.
Product must be equipped with special cooling provisions for
operation above this temperature.
Maximum ambient storage
temperature
60°C (140°F)
Maximum humidity,
operating or storage
95%, non-condensing.
Agency approvals or
certifications on components
All components are UL component recognized and can be used to
develop a cUL Listed to UL508A system when designed and built by
a qualified UL certified facility. Components can also be developed
for CSA-C2.2 No. 14 when authorized by CSA.
Insertion Impedance of the
series line reactor
+/- 10% at full load current
Table 10 lists the major technical specifications and intended environments for the KPC Panelized
Capacitors. Please see separate KPC IOM Manual (27908) for more detail.
Table 10 KPC Panelized Capacitors Technical Specifications
Voltage ratings 3-phase; 240, 380-415, 480, 600 Volt
kVar ratings 3 to 270 kVar depending on voltage.
Agency approvals UL Listed; File E-116124
Capacitors Oil filled high endurance design (no PCBs)