II. Features
1. Using advanced wireless transceiver technology, signal transmission can be completed without wiring, and the
project is simple and convenient.
2. Using 470MHz frequency band communication, FSK coding technology, strong anti-interference ability, long
transmission distance;
3. With battery low-voltage detection, remind users to replace when the battery is insufficient to maintain the
detector's normal operation.
4. The use of high-sensitivity thermal elements improves the response speed of the temperature detector to
temperature changes.
III. Technical Specifications
1. TypeA2R
2. Battery type CR17450 3V
3. Working Current Standby Current3uA
Alarm Current18mA
4. IndicatorsFire Indicatorred, always on when it alarms
Fault Indicatoryellowflash twice every 48s when the battery is undervoltage. Periodic flashing
when communication fails after entering the network
Working IndicatorGreen, flashing periodically when the communication is normal after entering
the network
5. Coding methodThe control panel is automatically assigned during networking
6.Communication method470MHz FSKCoded two-way communication
7.Communication distance:≤50m
8.Transmitting power: <20dBm
9. Frequency band:470MHz
10. Protection area: When the height of the space is less than 8m, the protection area of a detector is 20m2
30m2 for the general protection site. The specific parameters should be based on the "Code for Design of
Automatic Fire Alarm System" (GB 50116-2013).
11. Use environment:
Atmosphere pressure86kPa106kPa
Temperature-10℃~+50
Relative humidity95%non-condensing
12. Dimensions: diameter 100mm, high 54mm (with base)
13. Protection grade: IP30