Tus neeg siv phau ntawv
Table Of Contents
- I. General
- III. Technical Specifications
- IV. Structure and Working Principle
- 2. Working principle
- The detector uses a high-precision thermistor sens
- V. Installation
- 1. Points for on-site installation
- The wireless performance indicators of this produc
- VI. Test
- Warning: Please make sure that the polarity of the
- 1. The detector must be tested after installation
- 2. Simulated fire alarm: After successfully connec
- 3. During the test, the unqualified detector shall
- VII. Use and Operation
- 1. Network segment setting: Before the detector co
- 2. The device enters and exits the network: After
- A) Network access operation: When the control pane
- B) Network exit operation: When the control panel
- 3. Equipment alarm: When the temperature in the en
- 4. Device reset: When the device reports a fire al
- 5. Restore factory settings: After the detector is
- Note: The button function only has one click, thre
Yingkou Tiancheng Fire Protection Equipment Co., LTD
II. Features
1. Using advanced wireless transceiver technology, signal transmission can be completed without wiring, and the
project is simple and convenient.
2. Using 470MHz frequency band communication, FSK coding technology, strong anti-interference ability, long
transmission distance;
3. With battery low-voltage detection, remind users to replace when the battery is insufficient to maintain the
detector's normal operation.
4. The use of high-sensitivity thermal elements improves the response speed of the temperature detector to
temperature changes.
III. Technical Specifications
1. Type:A2R
2. Battery type: CR17450 3V
3. Working Current: Standby Current≤3uA
Alarm Current≤18mA
4. Indicators:Fire Indicator:red, always on when it alarms
Fault Indicator:yellow,flash twice every 48s when the battery is undervoltage. Periodic flashing
when communication fails after entering the network
Working Indicator:Green, flashing periodically when the communication is normal after entering
the network
5. Coding method:The control panel is automatically assigned during networking
6.Communication method:470MHz FSKCoded two-way communication
7.Communication distance:≤50m
8.Transmitting power: <20dBm
9. Frequency band:470MHz
10. Protection area: When the height of the space is less than 8m, the protection area of a detector is 20m2~
30m2 for the general protection site. The specific parameters should be based on the "Code for Design of
Automatic Fire Alarm System" (GB 50116-2013).
11. Use environment:
Atmosphere pressure:86kPa~106kPa
Temperature:-10℃~+50℃
Relative humidity≤95%,non-condensing
12. Dimensions: diameter 100mm, high 54mm (with base)
13. Protection grade: IP30