User's Manual

Proprietary and Confidential 2006.02.08
8
2.5 Mount the meter module
2.5.1 TC-1205/TC-1207 Meter Module (electromechanical meters)
1. Attach the connector of the IR serial interface to the mating connector on the meter module. Take care to align the
keys on the connector to the slots on the socket.
2. The connector should snap into place. Do not force the connector into place. If force is necessary then the keys are
likely not aligned with the slots in the socket.
3. Position the module over the mounting posts on the meter.
4. Position the nameplate over the module. Use the ½” mounting screws for GE I-70, or the original nameplate
mounting screws for the ABB AB-1, and secure the module to the mounting posts.
Figure 6: Connect the IR Serial Interface
5. Select the appropriate power clips for the size of the bus bars in the meters which are being retrofitted.
6. Use needle nose pliers to attach a pair of power clips to the Fast-on tabs on the meter module power leads.
7. Crossover the power leads to put three twists in the leads and arrange the leads together around the right side of the
meter
8. Attach the power clips to the bus bars at the top side of the meter as shown in the figure below.
9. Use a flat screwdriver to press the clips onto the bus bars.
10. Replace the glass or polycarbonate cover for the meter.
Figure 7: Connect the Power Leads to the Meter Power Bus Bars
IR Serial Interface