User's Manual
4
Installing the TC-2200
BEFORE YOU BEGIN
1. Assemble the necessary equipment: Tantalus TC-2200 Module Installation Kit and
required tools and materials.
TC- 2200 MODULE INSTALLATION KIT
Each kit for installing a Tantalus TC-2200 module includes the following items:
• One TC-2200 module
• One IR serial interface
In addition to the retrofit kit the following items are required:
• Mounting screws for GE I-70-S meter: UNF 4-48 x ¾” (Two required per meter)
• Mounting screws for ABB AB-1 meter: UNF 6-40 x ¾” (Two required per meter)
• Power clips to attach to bus bars (Two required per meter): Part number dependant on
bus bar diameter.
Tantalus P/N Bus Bar Diameter
13811300003A 0.20” – 0.22”
13811300003B 0.18”
13811300003C 0.26” – 0.28”
13811300003D 0.32” – 0.36”
REQUIRED TOOLS AND MATERIALS
• 3/8” electric hand drill and 3/8” drill bit
• Drill alignment jig (recommended for GE meters)
• Needle nose pliers
• #2 Phillips screwdriver
• Rubbing alcohol
• Soft cloth or paper towels
• Disk marking template and paint pen
• Anti-static wrist strap
• Computer for programming TC-2200 module (Desktop, laptop or handheld
computer)
• Tantalus TC-2200 module programming software
• DC power supply, 6 – 8 VDC, for powering the module for programming
• TC-2200 Programming Cable