User's Manual
NC-2202 Installation Guide
P/N 900.000 Proprietary and Confidential
11
5 Initial Configuration and Testing
5.1 IP Address Configuration
All configuration of the NC-2202 is normally done through the HTTP web interface from the NS-2000 Network Server. In
order for the server to connect to the NC-2200 the IP configuration of the NC-2202 Network Controller must be done. A
local monitor, keyboard and mouse are required to complete the IP configuration. This is the only time the monitor, keyboard
and mouse will be required.
With the monitor, keyboard and mouse connected login to the NC-2202 as root with the root password. Start a Phindows
session by typing “ph”. Under Configure click on the Network tab then click on the Devices tab. Configure the following
information:
- Connection: Manual
- IP: enter the assigned static IP address
- Netmask: enter the required netmask
From the Network tab configure the following:
- Host name: enter the host name, usually the site name
- Domain name: not required
- Default Gateway: enter the IP address of the default gateway
- Name servers: At least one name server IP address is required. Enter the IP address of a name server in the
IP field and click the Add button to add the name server.
5.2 Server connection
The NC-2202 configuration screens are on the NS-2000 server. The TCP/IP connection must be established between the
server and the Network Controller in order to access these screens.
Configure the IP configuration on the server following the same steps described above.
Establish the TCP/IP connection between the server and the Network Controller.
5.3 Configure the Network Controller Frequency and Power Level
Refer to the NC-2202 Network Administrators guide for a description of the configuration screens for the Network
Controller. An assigned username and password are required to access the server and the Network Controller.
5.4 Initial Tests
Perform the following initial tests to put the NC-2202 into service:
• Check the base station power output
• Check the transmitter modulation levels
• Test the receiver 12 DB SINAD sensitivity
• Test for receiver desensitization during full duplex operation
• Perform initial Packet Error Rate tests with a remote TUNet 3205 WAN Transceiver