Technical Data
TECHINCAL DATA SHEET 
Cape Backdraft Damper 
Fabric 
Testing was conducted in accordance with the ASTM International fire test response standard E 84-07, Surface 
Burning Characteristic Of Building Materials, sometimes referred to as the Steiner tunnel test.   This test is 
applicable to exposed surfaces such as walls and ceilings. The ASTM E84 test method is technically equivalent 
to NFPA No. 255 and UL No. 723. 
TEST RESULTS: 
The test results, calculated on the basis of observed flame propagation and the integrated area under the recorded smoke density curve, 
are presented below. The Flame Spread Index obtained in E 84 is rounded to the nearest number divisible by five. Smoke Developed 
Indices are rounded to the nearest number divisible by five unless the Index is greater than 200.  In that case, the Smoke Developed 
Index is rounded to the nearest 50 points.  
Test Results 
Test specimen 
Flame Spread 
 Index 
Smoke Density 
Developed 
Fiber-Reinforced Cement Board Grade II 
 0 
 0 
Red Oak Flooring 
100 
100 
TAMARA110207A 
 15 
 25 
Observations 
Specimen ignition over the burners occurred at 0.03 minutes. Surface flame spread was observed to a maximum distance of 2.77 feet 
beyond the zero point at 0.20 minutes. The maximum temperature recorded during the test was 517°F. 
Classification 
The Flame Spread Index and Smoke Development Index values obtained by the ASTM E 84 test are frequently used by code officials 
and regulatory agencies in the acceptance of interior finish materials for various applications. The most widely accepted classification 
system is described in the National Fire Protection Association publication NFPA 101 Life Safety Code, where: 
Class A 
 0-25 Flame Spread Index 
0-450 Smoke Developed Index 
Class B 
 26-75 Flame Spread Index 
0-450 Smoke Developed Index 
Class C 
 76-200 Flame Spread Index 
0-450 Smoke Developed Index 
Class A, B, and C correspond to Type I, II, and III respectively in other codes. They do not preclude a material being otherwise 
classified by the authority of jurisdiction. 
Tamarack Technologies, Inc. 
320 Main Street 
Buzzards Bay, MA 02532 
800-222-5932/508-759-4660 FAX: 505-759-6001 
www.tamtech.com 