Technical Data

TECHINCAL DATA SHEET
Cape Backdraft Damper
Fabric
Testing was conducted in accordance with the ASTM International fire test response standard E 84-07, Surface
Burning Characteristic Of Building Materials, sometimes referred to as the Steiner tunnel test. This test is
applicable to exposed surfaces such as walls and ceilings. The ASTM E84 test method is technically equivalent
to NFPA No. 255 and UL No. 723.
TEST RESULTS:
The test results, calculated on the basis of observed flame propagation and the integrated area under the recorded smoke density curve,
are presented below. The Flame Spread Index obtained in E 84 is rounded to the nearest number divisible by five. Smoke Developed
Indices are rounded to the nearest number divisible by five unless the Index is greater than 200. In that case, the Smoke Developed
Index is rounded to the nearest 50 points.
Test Results
Test specimen
Flame Spread
Index
Smoke Density
Developed
Fiber-Reinforced Cement Board Grade II
0
0
Red Oak Flooring
100
100
TAMARA110207A
15
25
Observations
Specimen ignition over the burners occurred at 0.03 minutes. Surface flame spread was observed to a maximum distance of 2.77 feet
beyond the zero point at 0.20 minutes. The maximum temperature recorded during the test was 517°F.
Classification
The Flame Spread Index and Smoke Development Index values obtained by the ASTM E 84 test are frequently used by code officials
and regulatory agencies in the acceptance of interior finish materials for various applications. The most widely accepted classification
system is described in the National Fire Protection Association publication NFPA 101 Life Safety Code, where:
Class A
0-25 Flame Spread Index
0-450 Smoke Developed Index
Class B
26-75 Flame Spread Index
0-450 Smoke Developed Index
Class C
76-200 Flame Spread Index
0-450 Smoke Developed Index
Class A, B, and C correspond to Type I, II, and III respectively in other codes. They do not preclude a material being otherwise
classified by the authority of jurisdiction.