Installation Sheet
11 Page
WARNING FOR INSTALLATIONS
FOR YOUR SAFETY, READ BEFORE INSTALLATION:
Do not install the heater where water, debris or
flammable vapors may get into the flue terminal.
This may cause damage to the heater and void the
warranty.
Do not have the vent terminal pointing toward
any opening into a building. Do not locate your
heater in a pit or location where gas and water
can accumulate.
Do not install this water heater under an
overhang less than 3 ft (914 mm) from its top
or eaves. The area under an overhang must be
open to three sides (Outdoor model only).
Do not install the water heater vent terminator
within 1 ft (305 mm) from above opeing of air
intake or building and within 4 ft (1,219 mm) from
below or side opening of air intake or building in
USA, and within 3 ft (914 mm) in Canada of any air
intake or building opening (Outdoor model only,
refer to p. 28).
Do not install next to a dryer or any source
of airborne debris that can be trapped inside
the combustion chamber, unless the system is
direct-vented.
Prohibited
Prohibited
3 ft
(914 mm)
1 ft (305 mm) USA
3 ft (914 mm) Canada
4 ft (1,219 mm) USA
3 ft (914 mm) Canada
4 ft (1,219 mm) USA
3 ft (914 mm) Canada
Installaon
Installaon Manual
Water heater vent terminator must be at least 2
ft (610 mm) away from an inside corner for both
outdoor installation and direct-vent installation.
Inside
Corner
2 ft
(610 mm)
4 ft (1,219 mm) USA
3 ft (914 mm) Canada