Space Heating Applications
WARNING
Toxic chemicals used in boiler treatments such as alcohol, glycerol and glycol group
must not be introduced into the system when used for open loop potable water and
space heating.
The FLASH T-K3-OS/SP can be used to supply potable water and space heating and
shall not be connected to any heating system or component(s) previously used with
non-potable water where any chemicals were added to the water heating appliances.
When the system requires water for space heating at temperatures higher than required
for other uses, a means such as a mixing valve shall be installed to temper the water for
those other uses in order to reduce scald hazard potential.
Water temperature over 125 °F can cause severe burns instantly or death from scalds.
Chemicals such as diluted Glycol can be used for radiant floor, Hydro/fan coil air or
Baseboard heating only. The diluted solution of glycol must contain LESS than 30% of
Glycol. Be aware that in closed-loop glycol systems, low pressure in the heat
exchanger can cause low-temperature boiling, resulting in excessive noise and damage
to the water heater. Consult with the glycol maker for specifications prior to use.
Re-circulation:
* Size the pump to provide about 2 GPM
through the system at 15 Ft of Head plus
applications and piping head losses. 2 GPM will
allow the system to operate at its optimal
performance. .
* If the application requires a higher re-
circulating flow rate, make sure that the re-
circulating flow rate is no greater than 4 GPM.
If the flow rate is too high, the system could be
damaged by erosion.