User Guide
20 Page
3inchventinstallaon
Vent length Direct vent
5 to 20 ft
(1.5 to 6.0 m)
(DEFAULT)
OFF
ON
1 2 3 4 5 6 7 8 9 10
No. 6 : ON
No. 7 : OFF
21 to 40 ft
(6.1 to 12.2 m)
OFF
ON
1 2 3 4 5 6 7 8 9 10
No. 6 : OFF
No. 7 : OFF
41 to 70 ft
(12.3 to 21.3 m)
OFF
ON
1 2 3 4 5 6 7 8 9 10
No. 6 : ON
No. 7 : ON
Vent length Single vent
5 to 45 ft
(1.5 to 13.7 m)
(DEFAULT)
OFF
ON
1 2 3 4 5 6 7 8 9 10
No. 6 : ON
No. 7 : OFF
46 to 70 ft
(13.8 to 21.3 m)
OFF
ON
1 2 3 4 5 6 7 8 9 10
No. 6 : OFF
No. 7 : OFF
4inchventinstallaon
Vent length Direct vent and Single vent
5 to 50 ft
(1.5 to 15.2 m)
(DEFAULT)
OFF
ON
1 2 3 4 5 6 7 8 9 10
No. 6 : ON
No. 7 : OFF
51 to 100 ft
(15.3 to 30.5 m)
OFF
ON
1 2 3 4 5 6 7 8 9 10
No. 6 : OFF
No. 7 : OFF
Direct vent
Single vent with room-air intake
Terminations
Wall
Hanger
Hanger
Termination
Wall
Hanger
Examplesofinstallaonof3inch&4inchvent
WARNING
• Adjust the appropriate DIP switches according to vent size and vent length as
shown below. DO NOT adjust the other DIP switches.
• Turn off the power supply to the water heater before changing the DIP
switch settings.
• Failure to observe these warnings could lead to carbon monoxide poisoning
or death.
Bank of DIP switches
Computer board
Horizontal installation
For details of the optional items, refer to the Installation manual for each optional item.
For clearance information, refer to pp. pp. 25 to 27.
Installaon
Installaon Manual