Installation Sheet

35 Page
-Dual-purpose hot water heang-
(Domestic and Space Heating):
Diagrammatic layout of radiant heating and domestic water heater per mass. code.
The recirculation pump is to provide no less than 2 GPM (7.5 L/min) and no more than 4 GPM (15 L/min)
through each activated unit in the system.
• Priority Control Devices such as a flow switch, an Aquastat or other
electronic controller can be used to prioritize the domestic water system over
the heating system.
• Follow all local codes, or in the absence of local codes, follow the most recent
edition of the National Standard Code, ANSI Z21.10.3.
• This illustration is a concept design only. The reference to the 1/8
th
hole in
check is only for the State of Massachusetts. There are a wide variety of
variations to the application of controls and equipment presented. Designers
must add all necessary safety and auxiliary equipment to conform to code
requirements and design practice. For more details, contact the manufacturer.
NOTICE
Installaon
Installaon Manual
120VAC
switch or
outlet
Hot water outlet
Unions
T-handlegasshut-ovalve
Check valve
Electronically controlled
pumpmer.Acvates
every 6 hours for
60 seconds. Wire to
product approved pump
HeangCoil
(used with air-handler)
Cold water supply
3" gas exhaust vent
(Discharge must
comply with local and
state codes). Can not
be common vented
with other appliances
An approved Temperature and Pressure
ReliedValve,TietoLocaonapprovedBy
LocalCodesandMustMeetBTURangof
water heater Model Used
Check valve will have
1/8" hole drilling in
clapperoponal
Atmospheric
vacuum
breaker
Shut-o
valve
Pressure
gauge
Apply correct thermal
expansion tank-size
perapplicaon
Shut-ovalves
Shut-ovalves
Check valves
Cold water inlet
Gas inlet
Water
lter
Drain
plug
Thermostacmixingvalve
Hot water
supply and
return to
heangcoil
System installed with reverse
acngaquastattoshutofan.
Suggested but not required by
248CMR
50’-0”maximumdistancefrom
water heater to fan coil and black.
(Develoed length) Not including
coilinheangunit
NSF-61 product
approved pump
Automactemperingdevice
must be installed below
the top of the water heater
as per manufacturers
recommendaons
Piping loop
between water
heater and fan
coil shall be in
compliance with
248CMR
Tempered water to
plumbingxtures.Must
meet temperature
requirementsof248CMR
All water piping should be insulated
inaccordancewith780CMR
(Massachusesenergycode)