Installation Sheet
17 Page
-Stainless steel Vent Illustraons-
<How to install stainless steel venting with the Direct Vent Indoor models>
• Regardingtheclearancesfromtheexhaustterminatortotheairinletoropening,refertothe
next few pages.
• Follow all vent system manufacturer’s instructions and all local codes.
• DonotcommonventorconnectanyventfromotherappliancestotheDirectVentIndoor
models vent.
• Use4”CategoryIII/IVapprovedorSpecialBH,singleordoublewallstainlesssteelventpipe.
HorizontalInstallaonDiagram
Wall
SidewallVent
Terminator
VercalInstallaonDiagram
Roof
Roof
Flashing
Fire stop
RainCap
4"ventconneconDiagram
Connect the 4" stainless steel vent
straight pipe directly on the
exhaust/Intake vent collar of the
water heater.
4”stainlesssteel
vent straight pipe
Exhaust vent collar
oftheDirectVent
Indoor models
(Female)
Intake vent collar
(Female)
4”stainless
steel vent
straight pipe
Diameter Max. No. of Elbow Max. Vertical and Horizontal (Total) Vent Length
4 in. (102 mm) 5 100 ft. (30.5 m )
*For each elbow added, deduct 5 ft. (1.5 m) from max. vent length.
No. of Elbows Max. Vertical or Horizontal Vent Length
0 100 ft. (30.5 m)
1 95 ft. (29.0 m)
2 90 ft. (27.4 m)
5 75 ft. (22.9 m)
Excludeselbowtermination,raincaps,orthe4in.(102mm)PVCConcentricTermination