Installation Sheet
15 Page
• Themaximumlengthofexhaustventpipingmustnotexceed70ft.(21.3m)for3”venting,which
depends on elevation where the water heater installaed. See the table below and 100 ft. (30.5
m)for4”venting(deducting5ft.(1.5m)foreachelbowusedintheventingsystem).Donotuse
more than 5 elbows.
• When the horizontal vent run exceeds 5 ft. (1.5 m), support the vent run at 3 ft. (0.9 m) intervals
with overhead hangers.
-PVC Venng Illustraons-
For details of the optional items, refer to the Installation manual for each Optional item.
Installaon
Installaon Manual
No. of Elbow
Max. Vertical or Horizontal (Total) Vent Length
3" venting 4" venting
Up to 3,000 ft Up to 6,000 ft Up to 10,100 ft Up to 10,100 ft
0 70 ft. (21.3 m) 40 ft. (12.2 m) 25 ft. (7.6 m) 100 ft. (30.5 m)
1 65 ft. (19.8 m) 35 ft. (10.7 m) 20 ft. (6.1 m) 95 ft. (29.0 m)
2 60 ft. (18.3 m) 30 ft. (19.1 m) 15 ft. (4.6 m) 90 ft. (27.4 m)
5 45 ft. (13.7 m) N/A N/A 75 ft. (22.9 m)
Diameter Max. No. of Elbow Max. Vertical and Horizontal (Total) Vent Length
3 in. (76 mm) 5 70 ft. (21.3 m)
4 in. (102 mm) 5 100 ft. (30.5 m)
*For each elbow added, deduct 5 ft. (1.5 m) from max. vent length.
Excludeselbowtermination,raincaps,orthe3in.(76mm)/4in.(102mm)PVCConcentricTermination
FordetailsontheventconnectiontotheDirectVentIndoormodels,refertoP.16.
HorizontalInstallaonDiagram
VercalInstallaonDiagram
Roof
Flashing
Roof
Fire stop
Wall
ConnectbetweenexhaustventcollarandPVCpiping
Seethenextpageforinstrucons.