Spec Sheet

Residential/Commercial Gas
Condensing High Efficiency
Tankless Water Heaters
Page 6 of 6 www.takagi.com TRGSS01512
Copyright Takagi 2012 Printed in U.S.A.
TAKAGI TANKLESS WATER HEATERS
500 Wald, Irvine, CA 92618
Toll Free: (888) 882-5244
Fax: (949) 770-3171
PRESSURE LOSS
0
20
40
60
80
100
120
0
5
10
15
20
25
30
35
40
45
50
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
Pressure Loss (psi)
Head (Feet)
0
20
40
60
80
100
120
0
5
10
15
20
25
30
35
40
45
50
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
Head (Feet)
Pressure Loss (psi)
T-H3J-DV/OS
T-H3S-DV/OS
0
20
40
60
80
100
120
0
5
10
15
20
25
30
35
40
45
50
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0
Head (Feet)
Pressure Loss (psi)
Flow rate (GPM)
Set temperature 125˚F (52˚C) or lower
Set temperature 130˚F (55˚C) or higher
T-H3-DV/OS
Pressure Loss
Flow Rate (GPM)
Pressure Loss
Flow Rate (GPM)
Pressure Loss
Flow Rate (GPM)
Specification
Water heater(s) shall be Model____________________ as manufactured by Takagi Water Heaters, shall be a copper coil integral fin and tube construction with quick release brass or bronze
waterways. Heater(s) will be factory assembled and tested.
The heater shall be vented with 3” or 4” Schedule 40 PVC, CPVC, or ABS vent pipe, or stainless steel Category III vent pipe at a distance not to exceed 70’ (equivalent) for 3” vent or 100’
(equivalent) for 4” vent, terminating vertically or horizontally as prescribed. Intake air pipe may be of such material as ABS, PVC, galvanized B-Vent, corrugated aluminum or stainless steel,
or Category lll / IV stainless steel not to exceed 70’ (equivalent) for 3” vent or 100’ (equivalent) for 4” vent.
The heater(s) shall be controlled by an onboard solid-state printed circuit board monitoring incoming and outgoing temperatures with factory installed thermistors, sensing and controlling
flow rate to set point temperature, controlling both air and gas mixture inputs to maintain thermal combustion efficiency. The heater(s) shall also consist of inline fusing, a spark ignition
and sensor system, aluminized stainless steel burners, an air-fuel ratio sensor, a hi-limit temperature switch, modulating and proportional gas valves, a freeze protection sensor with ceramic
heating blocks, and an overheat cutoff fuse.
The water heater(s) shall be CSA listed, exceed the energy efficiency requirements of ASHRAE 90.1b-1992, and shall comply with SCAQMD Rule 1146.2 Ultra-Low NOx Standards.