Install Instructions
Installation
20│Page
‐Pressurereliefvalve‐
Thewaterheaterhasahigh‐temperatureshutoffswitchbuiltinas a standard safety feature(calleda
Hi‐Limitswitch)thereforea“pressureonly”reliefvalveisrequired.
Thisunitdoesnotcomewithanapprovedpressurereliefvalve.
Anapprovedpressurereliefvalvemustbeinstalled
onthehotwateroutlet.
ThepressurereliefvalvemustconformtoANSIZ21.22orCAN1‐4.4andinstallationmustfollow
localcode.
The discharge cap acity must be at least 199,000 BTU/h for th e 520 (T‐H2) models, and 180,000
BTU/hforthe320(T‐H2S)models.
Thepressurereliefvalveneedstoberatedforamaximumof150psi.
Thedischargepipingforthepressurereliefvalvemustbedirectedsothatthehotwatercannot
splashonanyoneoronnearbyequipment.
Attach the discharge tube to the pressure relief valve and
run the end of the tube to within 6"
from the floor. This discharge tube must allow free and complete drainage without any
restrictions.
Ifthepressurereliefvalveinstalledonthewaterheaterdischargesperiodically,thismaybedue
toadefectivethermalexpansiontankordefectivepressure
reliefvalve.
Thepressurereliefvalvemustbemanuallyoperatedperiodicallytocheckforcorrectoperation.
Novalvemustbeplacedbetweenthereliefvalveandthewaterheater.
CONDENSATEDRAIN
Thewaterheaterdoesnotincludeabuilt‐incondensateneutralizercartridgeforreducingthepH
levelofcondensatewater.Iflocalcodesdictatethatcondensatemustbeneutralizedpriorto
drainage,acondensateneutralizermustbeinstalled.AnaccessoryNeutralizerassemblyissold
separately.
Intheabsenceof
applicablelocalcodesandregulations,themanufacturerrecommendsthat
condensatebedisposedofintoastandarddrain.Connectadraintubefromthecondensatedrain
port(shownbelow)locatedonthebottomofthewaterheatertoastandarddrain.
Follow all code requirements
of the local authority on
condensate neutralizers and
whether or not they are
requiredfortheinstallation.
Condensatedrainport