CASE 3: Wrong connections between the "CHILD-1" unit and the "CHILD-2" unit
• If you connect the “PARENT connector of the “CHILD-1” unit to the “1” connector of the
“CHILD-2” unit, the “CHILD-2” unit will operate as an individual unit, and will not be part of the
Easy-Link System.
CASE 4: Remote controller connected to incorrect unit
• Remote controller has to be connected to the “PARENT unit. If the remote controller is
connected to a “CHILD unit, it will only control that particular individual “CHILD” unit and will
not control the Easy-Link System as a whole.
Connecting two “PARENT connectors together from two separate units may
damage the computer board. The communication cable has a female end and
a male end so its impossible to have a PARENT-to-PARENT connection with the
communication cable. Do not splice or modify connectors.
WARNING