Installation Sheet
9 Page
CLEARANCES
OPTIONAL ITEMS
#
Model
Indoor Installation
Outdoor Installation
1. Remote controller: 100112155 (TM-RE30)
✓
✓
(Remote should be installed
indoors.)
2 Multi-unit Controller: 100112691 (TM-MC02)
✓ ✓
3.
5" (127 mm) Backflow preventer and F-F adaptor
100112598
✓
5" (127 mm) Universal Appliance Adaptor, F-F adaptor,
backflow preventer, condensate drain trap
2SVBFDPA05
✓
4. Vent cap: 100112194 (TM-VC50)
✓
5. Direct-vent conversion kit: 100112186 (TM-DV50)
✓
6. Pipe cover: 100112190 (TM-PC50)
✓ ✓
7.
5" Sidewall vent termination (Hood)
100112594/2NVTH5
✓
5" Wall thimble
(Refer to the next page.)
✓
8.
Direct-vent concentric termination
(Refer to the next page.)
✓
Installaon
Installaon Manual
INCLUDED ACCESSORIES
Installation manual
and Owner’s guide
Communication cable
100076417
Qty: 1
Qty: 1
Installation Top Bottom Front Back Sides
Indoor installation
12 in.
(305 mm)
12 in.
(305 mm)
4 in.**
(102 mm)
1.0 in.
(25 mm)
3 in.
(76 mm)
Outdoor installation
36 in.
(914 mm)
12 in.
(305 mm)
24 in.
(610 mm)
1.0 in.
(25 mm)
3 in.
(76 mm)
*Standard indoor installations and direct-vent indoor installations have the same clearances.
**24 inches recommended for maintenance.
***For the multiple installation of outdoor models, refer to the above clearances.
Maintain all clearances around the water heater.
Failure to do so could create a fire hazard, potentially leading to death, seri-
ous injury, and/or property damage.
WARNING