Installation Sheet

18 Page
Direct vent installaons
Vercal Installaon
Roof

Roof
Fire stop
Hanger
Vertical condensation
drain**
Backflow preventer*
Rain cap
Horizontal Installaon
Wall
Sidewall vent

Vertical condensation drain**
Back flow preventer*
Hanger
Installaon
Installaon Manual
-Clearances for sidewall terminaons-
NOTE: Refer to page 14 for the correct DIP switch settings.
Exhaust and/
or direct
vent sidewall
terminations
should be at least
2 ft (610 mm) away
from an opposite
surface/wall. Do
not place the
termination directly
in front of an opening
into a building.
Ancipated Snow level
Exhaust
Terminaon
2
(610 mm)
min.
1
(305 mm)
min.
1
(305 mm)
min.
Inside
corner
Exhaust
termination
2 ft (610 mm) min.
Inside
corner
Ancipated Snow level
2
(610 mm)
min.
1
(305 mm)
min.
1
(305 mm)
min.
Combined
intake and
exhaust
terminaon
Multiple Sidewall Terminations
An exhaust termination must be
at least 1 ft (305mm) away from
another exhaust termination. An
exhaust termination must also be
at least 2 ft (610 mm) away from
an inside corner. (If the adjacent
wall is less than 2 ft (610 mm) of
length, the minimum required
distance away from the inside
corner will be equal to the length
of that adjacent wall.)
Multiple DV Sidewall
Terminations
A direct vent (DV) termination
must be at least 1 ft (305 mm)
away from other direct vent
terminations.
A direct vent termination must
also be at least 2 ft (610 mm)
away from an inside corner. (If
the adjacent wall is less than
2 ft (610 mm) of length, the
minimum required distance
away from the inside corner will
be equal to the length of that
adjacent wall.)
*Backflow preventer (Recommended for freezing weather conditions:
36 °F (2 °C) and below).
**Vertical condensation drain must be installed in accordance with
local codes.
Improper installation can result in carbon monoxide poisoning or death. Follow all local
and national codes in regards to proper termination clearances. In the absence of such
codes, the clearances below must be met. Local codes supersede these clearances.
Failure to observe this warning may result in severe personal injury or death.
WARNING
Direct vent sidewall
terminations
that use two separate
penetrations for
the intake and
exhaust, distance the
intake and exhaust
terminations at
least 3 ft (915 mm)
away from each
other, no matter the
orientation.
Ancipated Snow level
3
(915 mm)
min.
3
(915 mm)
min.
1
(305 mm)
min.
Air supply
inlet
Air supply
inlet
Air supply
inlet
Exhaust
terminaon