Install Instructions
CAUTION: Do not attempt to remove LED panel from circulator. Serious damage to circulator electronics may result.
ATTENTION: N'essayez pas de retirer le panneau de LED du circulateur. Des dommages sérieux à l'électronique du circulateur peuvent
en résulter.
6
5
10
15
Max
Q(gpm)
012 3 4567 8 910111213141516
H (ft)
0
2
4
6
8
10
12
14
16
18
20
Q (l/s)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
H (m)
0
1
2
3
4
5
6
Q (m
3
/h)
432
1
0
008
0015 – Med
0
07
0015 – Low
006
Flow
Head in Feet
CONSTANT PRESSURE MODE ( ) – Variable Speed
In Constant pressure mode ( ), the circulator maintains a constant pressure differential (∆p-c) in the system as heating load
increases or decreases. Selection options are 5, 10, or 15 feet of head constant pressure. See chart above for equivalent 00
model at each setting.
Low
Med
High
Max
Q(gpm)
012 3 4567 8 910111213141516
H (ft)
0
2
4
6
8
10
12
14
16
18
20
Q (l/s)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
H (m)
0
1
2
3
4
5
6
Q (m
3
/h)
43
2
10
Flow
Head in Feet
PROPORTIONAL/VARIABLE PRESSURE MODE ( ) – Variable Speed
In Proportional/variable pressure mode ( ), the circulator maintains a proportional pressure differential (∆p-v) as heating load
increases or decreases. Flow will change in relationship to the change in pressure differential. Selection options are Low,
Medium, or High. If unsure on proper setting, select Medium
and adjust as needed.
Orange
LED
Green
LED