Install Instructions

US Patents 6,904,800, 7,243,540,
and 7,317,993
Other Patents Pending
General:
The Residential Low Water Cutoff (LTR) is a microprocessor based
low water cutoff for detecting the presence to water in a boiler. The
LTR uses advanced signal processing to identify when the probe
signal levels have decreased due to possible fouling. These advanced
technologies permit extended operation for probe impedance up to 40K
Ohms. The LTR functions longer without requiring probe cleaning, and
it functions normally under non-ideal installation conditions. The LTR is
designed for use with hot water boilers and hot water heating boilers.
(See each boiler manufacturers' specications for recommended
minimum safe water levels.)
During a low water condition, the "Status" LED will illuminate RED.
Under normal conditions, it will illuminate GREEN. See "Status LED
States" table for details.
Instruction Sheet
LTR - Low Water Cutoff
for Hot Water Boilers
102-338
SUPERSEDES: Revision F Dated December 17, 2012
#5401179-REV G PLANT ID 001-3907
EFFECTIVE: June1, 2017
Listings/Approvals
• UL GUIDE (MBPR) for Limit Controls per UL Standard
353 Limit Controls
• UL GUIDE (MBPR7) Controls, Limit Certied for Canada
CSA Standard C22.2
Maximum Probe Ratings:
Hot water only - 160 psi (11.2kg/cm
2
) at 250°F (121°C)
Probe Sensitivity: 20K Ohms. Extended operation to 40K Ohms.
Ambient Temperature: 32°F - 120°F (0°C to 49°C)
Enclosure Rating: NEMA 1 for indoor use only
Input Power: 1.5 VA @ 24 VAC supplied by a Class 2 power source
Output Contact: Form B Relay, normally closed (water detected)
LTR024 Models
5A @ 24VAC Max Load
50 VA @ 24VAC Switching
Reset:
Automatic Model: Automatic reset when water level returns to safe
level
Manual Model: Press RESET Button when water level returns to safe
level
Testing: Integrated test switch for testing safety shutdown
• Installation must be performed by qualied personnel and in accordance with all national and local codes and ordinances.
• Read all instructions carefully and understand them before starting installation. Save instructions for future use.
• Instruct user how to test and operate this cutoff device as described in these instructions.
• Risk of explosion. Not for use in hazardous locations. Serious injury or death could result.
• The LWCO device must be installed in series ahead of other limit and operating controls installed on the boiler. When installations are complete,
check for correct operation of ALL limit and operating controls.
• For use with hot water boilers and hot water heating boilers only. Use on steam boilers could cause improper operation resulting in property damage,
serious injury, and death.
• Shock Hazard. Disconnect power source before servicing. Serious injury or death could result.
• Use only the wiring harness supplied with the control or factory supplied alternates. Use of other wire harness or insulation types could result in re
causing property damage, serious injury, or death.
• Hot or pressurized boiler systems can discharge steam and hot water. Cool boiler system to 80º F (27º C) and to 0 psi (0 bar) before servicing.
Failure to do so could result in serious burns.