Install Instructions

Programming EWF
Three DIP style switch blocks program the EWF operation mode.
Factory settings (shown above):
MODE = LWCO
DBF = 2 minutes
Excess Feed = Disabled
FF = 1 Gallon
HAW = 0 delay
DEFINITION OF DELAYS (SEE FIG. 8)
The amount of time before the
EWF starts feeding once a low
water condition has been detected
by the low water cutoff.
The amount of time before the
EWF stops feeding after a normal
water condition has been detected
by the low water cutoff. This delay
allows the EWF to feed additional
water to the boiler after the LWCO
is satisfied, and it is only available
when the EWF is in LWCO mode.
Use this setting when a water level
higher than that set by the LWCO
is required or if the LWCO does
not have an appropriate delay on
make, (DOM), feature.
Water Feeding Period The amount of time that the EWF
feeds the boiler. The EWF feeds 1
gallon each minute**.
** The EWF will feed 1 gpm for inlet pressures of 20
to 120 PSI as long as the inlet/outlet pressure
differential is at least 20 PSI. (For example, with a
boiler pressure of 15 PSI, the inlet pressure of the
EWF should be at least 35 PSI.) When pressures fall
outside this range, test the system and set the
EWF operating controls to compensate for your
application.
FIG. 8
FIG.9 (a):Delay Before Feed Mode (b):Excess Feed Mode (c):Fixed Feed and Hold
After Water OK Mode
(5)
DBF
(Delay Before Feed)
HAW
(Hold After Water OK)
Water Feeding Period
Low Water Period
Delay Before Feeding
Period (DBF)
Hold Period After
Water OK, (HAW)
Normal Water
Condition
Low Water
Condition
Feed Valve
Closed
Feed Valve
Open
ONOFF
1
2
3
4
5
6
7
8
1 Min.
0.5 Min.
4 Mins.
2 Mins.
8 Mins.
6 Mins.
FF LWCO
10 Mins.
OFF ON
DELAY BEFORE FEED
(DBF)
MODE
ALL OFF = 0 DELAY
S1
ONOFF
1
2
3
4
5
10 Gals.
8 Gals.
15 Gals.
12 Gals.
6 Gals.
OFF ON
EXCESS FEED SETTING
ALL OFF = DISABLED
S4
ONOFF
1
2
3
4
5
6
7
8
3 Gals.
2 Gals.
5 Gals.
4 Gals.
1 Gal.
OFF ON
FIXED FEED AMOUNT
(FF)
1 Min.
0.5 Min.
2 Mins.
HOLD AFTER
WATER OK
(HAW)
ALL OFF =
0 DELAY
S3
If all DBF switches are set to OFF, DBF delay is zero.
If all FF switches are set to OFF, the system will automatically feed 1 gallon.
If all HAW switches are set to OFF, HAW delay is zero.
If multiple switches are ON for DBF, Excess Feed, FF, or HAW, the lowest setting will be used.
See Fig. 2 for location of the programming switches.
If programming the EWF to operate in Fixed Feed Mode, be
sure to follow the procedure Testing and Setting Fixed Feed
Systems before putting the system into service.
*MBH is thousands of BTU's
per hour
**Excess feed settings are
based upon normal boiler
operation throughout typical
heating seasons. These
recommended settings do not
account for water added due
to boiler maintenance.
Follow boiler manufacturers'
usage recommendations if
they differ from the settings
shown here.
gnitaRRBIteN
*HBM
dednemocceR
deeFssecxE
gnitteS
**)htnoM/slaG(
09otpU.slaG6
021-09.slaG8
051-021.slaG01
581-051.slaG21
rehgiH&581.slaG51