Install Instructions

Shock hazard. Disconnect power source
before servicing. Serious injury or death
could result.
EWF Wiring
Standard Wiring EWF to LWCO with same voltages, see
Figure 5.
1. Verify that the supply and burner circuit voltages con-
nected to the LWCO are the same as the EWF
2. Verify that factory-installed jumpers connecting the hot
lead on the LWCO to the burner source are installed.
3. Connect the hot lead wire from the power source to
terminal H on the EWF.
4. Connect the neutral lead wire from the power source to
terminal N on the EWF.
5. Connect the NO/water feeder/alarm terminal on the
LWCO to terminal LW on the EWF.
Wiring EWF to LWCO with different burner circuit voltages,
see Figure 6a & b.
1. Verify that the burner circuit voltages connected to the
LWCO are the same as the EWF
2. Verify that factory-installed jumpers connecting the hot
lead on the LWCO to the burner source are removed.
3. Connect the hot lead wire from the burner power source
to terminal H on the EWF.
4. Connect the neutral lead wire from the burner power
source to terminal N on the EWF.
5. Connect the NO/water feeder/alarm terminal on the
LWCO to terminal LW on the EWF.
NC COM NO H N
Taco LTx120x / LTx024x
GND P
BURNER
CIRCUIT
HOT
NEUTRAL
HN
Taco EWF120 / EW F024
LW
120 VAC / 24 VAC
CIRCUIT
FIG. 5
FIG. 6
(b)
(4)
(a)
NC COM NO H N
Taco LTx120x
GND P
BURNER
CIRCUIT
120 VAC
CIRCUIT
HOT
NEUTRAL
H N
Taco EW F024
LW
24 VAC
CIRCUIT
HOT
NEUTRAL
NC COM NO H N
Taco LTx024x
GND P
BURNER
CIRCUIT
120 VAC
CIRCUIT
HOT
NEUTRAL
H N
Taco EW F120
LW
24 VAC
CIRCUIT
HOT
NEUTRAL
*
*
* NOTE:
Remove factory installed
jumper between H and COM terminals
EWF Standard Wiring
EWF Alternate Wiring
FIG. 7
(a)
(b)
NC
COM
NO H N GND P
BURNER
CIRCUIT
HOT
NEUTRAL
HNLW
120 VAC
CIRCUIT
NHC WB
McDonnell & Miller
PS-801/851-120
w/Red & Green LEDs
1 23 45
McDonnell & Miller
PS-801/851-120 w/Red &
Amber LEDs, Series 750
21P1P2 A
Hydrolevel
450, 550, 650, & 750
Taco LTx120x
Taco EWF120
Installed
Jumper **
Taco LTx024x
Taco EWF024
NC
COM
NO H N GND P
BURNER
CIRCUIT
HOT
NEUTRAL
HNLW
24 VAC
CIRCUIT
21P1P2 A
Hydrolevel
400, 500, 600, & 700
NHC WB
McDonnell & Miller
PS-802/852-24
Installed
Jumper **
Wiring the EWF to Various LWCO's
Factory
Installed
Jumper
NOTE:
Wiring shown only for control
and burner circuits of the same
voltage. Some terminal designations
are not in their actual order on the
LW COs.
** May be factory installed on
some LWCOs