User Guide
ADJUSTING MAXIMUM TEMPERATURE (NON-ASSE 1070 APPLICATIONS):
NOTE: Maximum temperature must only be adjusted above 120° in installations
which are outside the scope of ASSE 1070.
To adjust the maximum temperature:
• Unscrew the retaining screw to remove the cap. (Figure 2)
• Lift the limit stop ring off of the spindle, rotate to the new maximum temperature posi-
t
ion and place the limit stop back on the spindle. (Figure 3)
•
Replace the cap and install the retaining screw. The valve may now be freely adjust-
ed up to the new maximum temperature.
HOT
COLD
COLD
MIX
COLD WATER LOOP
FLOW REGULATOR
12" RECOMMENDED
HOT
WATER HEATER
TYPICAL ASSE 1017 INSTALLATION:
WATER
HEATER
COLD WATER
SUPPLY
HOT WATER
SUPPLY
MIXED
TO FIXTURE COLD
MIXED
TO FIXTURE COLD
5120 SERIES 5120 SERIES
HC
M
HC
M
TYPICAL ASSE 1070 INSTALLATIONS:
WATER
HEATER
COLD WATER
SUPPLY
HOT WATER
SUPPLY
MIXED
TO FIXTURE
MIXED
TO FIXTURE
5120 SERIES 5120 SERIES
HC
M
HC
M
HANDLED FIXTURES HANDLESS FIXTURES
FLOW CHART: