User Guide
Instruction Sheet
5120-2 Series Lead Free (≤ .25% Pb) Mixing Valve
102-490
SUPERSEDES: New EFFECTIVE: August 1, 2013
Plant I.D. 001-4204
WARNING: Water temperatures above 120°F can cause serious injury. Mixing valve temperature setting should
be done by a licensed professional per local code requirements. Use an accurate water thermometer and ver-
ify the final water temperature. The thermostatic strip provided must not be used for final water temperature
verification.
WARNING: The 5120 Series must not be installed on steam systems (water systems only).
WARNING: 5120 Series mixing valves are not designed to compensate for system pressure fluctuations
beyond the valves variation rating and should not be used where more sophisticated pressure compensating
temperature controls are required. These mixing valves are not intended to provide protection against
thermal shock.
GENERAL:
The Taco 5120 Series is dual listed for both ASSE 1070 and ASSE 1017 applications.
• NOTE: Non-union NPT valve is ASSE 1017 only and does not have check valves.
• All installations should be carried out by a Licensed Professional. Failure to comply with all aspects of these instruc-
tions may result in unsafe performance. All installations must comply with relevant State and Local codes or
authorities.
• Ensure compatibility of valve installation, e.g. temperature of hot water, inlet pressure, flow rates, etc. - refer to spec-
ification section. If the site conditions are outside of the specifications for the valve, the site conditions must be cor-
rected or a valve that meets the conditions must be selected.
• Install in accordance with markings on valve body, i.e. hot water inlet - marked “H”, cold water inlet - marked “C” and
mixed outlet - marked with directional arrow.
• Valve may be installed in any position.
• Any inconsistency between these instructions and any specific instructions, bylaws or codes issued by local author-
ities must be referred back to Taco, Inc. prior to any installation taking place.
• During startup ensure that the valve is set to the desired temperature (valve preset at 115-120°F (46-49°C) with 150°F
(66°C) hot water inlet temperature). If the valve temperature needs to be adjusted please refer to the instructions below
(SETTING VALVE OUTLET TEMPERATURE).
NOTE: If the water supply is of poor quality a filter or strainer should be fitted at the system inlet so that both the
water heater and the mixing valve are protected from dirt and debris.
FITTING VALVE TO PIPING SYSTEM:
• Flush all piping thoroughly before installing the valve (using water only). Not flushing the system properly is the most
common cause of improper valve performance.
• Union valves come complete with union style connections for ease of installation and service. Non-union versions
have NPT threads built into the body.
• Valve must be removed from the piping prior to soldering the end connections. It is recommended to use a spacer piece
while soldering.
• For models using the temperature gauge and adaptor on the mixed outlet, attach the adaptor to the
mixing valve body, insert the temperature gauge into the adaptor well and then attach the valve union
connection to the adaptor.
SETTING VALVE OUTLET TEMPERATURE:
The Taco Series 5120 Mixing Valve is supplied factory set at 115-120°F with 150°F hot water inlet temper-
ature. It may need to be altered depending on operating requirements.
1. Rotate the green knob counterclockwise to increase the outlet temperature and clockwise to decrease
the outlet temperature. (See Figure 1)
2. Turn both the hot and cold water supplies on. Open the outlet closest to the mixing valve, preferably a
sink rather than a shower. To calibrate, let the water run for 2 minutes and measure the outlet temper-
ature with a thermometer. Adjust the outlet temperature to the desired setting.
3. A temperature strip is provided with each mixing valve and can be used as a reference to set the tem-
perature, however a more accurate device should be used to ensure a correct temperature setting.




