Specification Sheet
101-032
Model 009 Cartridge Circulator
Effective: January 12, 2015 Supersedes: May 8, 2013
Submittal Data Information
Job: Engineer:
Contractor:
Rep:
ITEM NO. MODEL NO. IMP. DIA. G.P.M. HEAD/FT. H.P. ELEC. CHAR.
Do your best work.
®
TACO INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 Fax: 942-2360
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3 Telephone: (905) 564-9422 Fax: (905) 564-9436
Visit our website at: www.taco-hvac.com
Printed in USA
Copyright 2015
TACO, Inc.
Features
• Standard high capacity
output-compact design
• Quiet, efficient operation
• Direct drive - Low power consumption
• Unique replaceable cartridge design
— Field serviceable
• Self lubricating
• No mechanical seal
• Unmatched reliability - Maintenance free
• Universal flange to flange dimensions
• Cast Iron or Stainless Steel construction
Materials of Construction
Casing (Volute): ............Cast Iron or St. Steel
Stator Housing: ............Aluminum
Cartridge: .........................Stainless Steel
Impeller: ...........................Non-Metallic
Shaft: ...................................Ceramic
Bearings: ...........................Carbon
O-Ring & Gaskets: ....... EPDM
Model Nomenclature
F – Cast Iron, Flanged
SF – Stainless Steel, Flanged
Performance Data
Max. Flow: 10 GPM
Max. Range: 35 Feet
Min. Fluid Temperature: 40˚F (4˚C)
Max. Fluid Temperature: 230°F (110˚C)
Max. Working Pressure: 150 psi
Connection Sizes:
3/4", 1", 1-1/4", 1-1/2" Flanged
Submittal Data Information
Model 009 Cartridge Circulator
Submittal Data # 101-032
Supersedes: 05/08/13
Effective: 01/12/15
Application
The Taco 009 is designed for a wide range of residential and light
commercial higher-head/lower-flow water circulating applications.
Typical uses include hydronic heating, radiant in-floor/panel heating and
closed-loop solar heating systems. The Stainless Steel 009 can be used
in higher-head/lower-flow heat recovery, open-loop solar heating and
light commercial domestic water recirculation systems. The unique
replaceable cartridge contains all of the moving parts and allows for easy
service, instead of replacing the entire circulator. Compact, direct-drive,
low power consumption design is ideal for high-efficiency jobs.
FLOW-GPM
024681012141618202224262830323436384042444648505254
TOTAL HEAD-FEET
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
FLOW-M3/H
0.0 0.6 1.2 1.8 2.43.0 3.64.2 4.85.4 6.06.6 7.27.8 8.4 9.0 9.610.210.811.412.0
TOTAL HEAD-METERS
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
009
0010
0011
0012
0013
0014
3
2
1
2
3
4
5
6
4
5
6
1
00
®
CIRCULATORS
Performance Field - 60Hz
F
D
G
C
A
B
Pump Dimensions & Weights
Electrical Data
Mounting Positions
Standard
Optional
OK if over
20 psi
Flange Orientation
Taco Inc., 1160 Cranston Street, Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com
Low-Lead Compliant
Certifications & Listings
FOR INDOOR
USE ONLY
Models Casing
A B C D F G
Ship Wt.
in. mm in. mm in. mm in. mm in. mm in. mm lbs. Kg
009-F5 Cast Iron
7
178 5-11/16 144
3-3/16
81
3-15/16
84 4-1/8 105 6-3/8 162 9.5 4.3
009-SF5 St. Steel
7
178 5-11/16 144
3-3/16
81
3-15/16
84 4-1/8 105 6-3/8 162 9.5 4.3
Model
Volts Hz Ph Amps RPM
HP
009-F5
115
60 1 1.40 3250 1/8
009-SF5
115
60 1 1.40 3250 1/8
Motor
Type
Permanent Split Capacitor
Impedance Protected
Motor
Options
220/50/1, 220/60/1, 230/60/1, 100/110/50/60/1