Submittal Sheet

Submittal Data Information
Model 007 Cartridge Circulators
Submittal Data # 101-029
Supersedes: 06/01/11
Effective: 03/25/13
Application
The Taco 007 is a cartridge style, maintenance free, wet-rotor, in-line, single stage
circulator pump. It is designed for quiet operation in Hydronic heating, Radiant
heating, Hydro-Air fan coils, Indirect water heaters, Chilled fresh water, and
Domestic Water Recirculation systems. Available in Cast Iron or Stainless Steel
construction with universal flanged connections. The unique replaceable cartridge
contains all of the moving parts and allows the circulator to be easily serviced
instead of replacing the entire unit. Ideal for a wide range of applications.
A
B
F
D
G
C
Electrical Data
Mounting Positions
Standard
*Flange Orientation Type
Optional
Standard (S)
Rotated (R)
OK if over
20 psi
Performance Field - 60Hz
Features
Standard High Capacity
Output-Compact Design
Quiet, Efficient Operation
Direct Drive-Low Power Consumption
Unique Replaceable Cartridge
Design-Field Serviceable
Self Lubricating
No Mechanical Seal
Unmatched Reliability-Maintenance Free
Universal Flange to Flange Dimensions
Cast Iron or Stainless Steel Construction
Materials of Construction
Casing (Volute): .......... Cast Iron or Stainless Steel
Stator Housing: .......... Steel
Cartridge: ....................... Stainless Steel
Impeller: ......................... Non-Metallic
Shaft: ................................. Ceramic
Bearings: ......................... Carbon
O-Ring & Gaskets: ..... EPDM
Model Nomenclature
F - Cast Iron, Flanged
SF - Stainless Steel, Flanged
Performance Data
Flow Range: 0 – 23 GPM
Head Range: 0 – 10 Feet
Minimum Fluid Temperature: 40˚F (4˚C)
Maximum Fluid Temperature:
Cast Iron: 240°F (115˚C)
Stainless Steel: 230°F (110˚C)
Maximum Working Pressure: 125 psi
Connection Sizes: 3/4", 1", 1-1/4", 1-1/2" Flanged
Taco Inc., 1160 Cranston Street. Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com
Pump Dimensions & Weights
Models Casing
Flange
Type*
A B C D F G
Ship Wt.
in. mm in. mm in. mm in. mm in. mm in. mm lbs. Kg
007-F5 Cast Iron S
6-3/8
162 4-1/2 114
3-3/16
81
3-15/16
75 4-3/4 121 6-3/8 162 8.0 3.6
007-F5-5 Cast Iron R
6-1/2
152 4-1/2 114
3-3/16
81
3-15/16
75 4-3/4 121 6-3/8 162 8.0 3.6
007-SF5 St. Steel S
6-3/8
162 4-1/2 114
3-3/16
81
3-15/16
75 4-3/4 121 6-3/8 162 7.0 3.2
Model
Volts Hz Ph Amps RPM
HP
007-F5
115
60 1 .71 3250 1/25
007-SF5
115
60 1 .75 3250 1/25
Motor
Type
Permanent Split Capacitor
Impedance Protected
Motor
Options
220/50/1, 220/60/1, 230/60/1, 100/110/50/60/1
Low-Lead Compliant
Certifications & Listings
FOR INDOOR USE ONLY