Submittal Sheet
50
0
5
10
15
20
25
30
35
10 15 20 25 30 35 40 45 50
Flow Rate Q [GPM]
Head
[ft.]
C2 = 12 ft.
C1 = 6 ft.
C5 = 30ft.
C4 = 24ft.
C3 = 18ft.
0034ePlus
High-Eciency Circulator
Constant Pressure Curves
50
0
20
60
80
40
100
120
140
160
180
10 15 20 25 30 35 40 45 50
Flow Rate Q [GPM]
Power [W]
C5
C3
C4
C2
C1
0034ePlus
High-Eciency Circulator
Constant Pressure Curves
Power Consumption
50 10 15 20 25 30 35 40 45 50 55
Flow Rate Q [GPM]
0
5
10
15
20
25
30
35
Head [ft.]
0034ePlus
High-Eciency Circulator
activeADAPT™ Range
activeADAPT
50 10 15 20 25 30 35 40 45 50 55
Flow Rate Q [GPM]
0
30
60
90
120
150
180
Power [W]
0034ePlus
High-Eciency Circulator
activeADAPT Range
Power Consumption
activeADAPT
activeADAPT™ Mode:
activeADAPT is an operating mode
designed for constant circulation
systems. On this setting, the circulator
will sense changes in system ow
and head conditions and adjust the
operating curve automatically.
Purple LED
activeADAPT
Constant Pressure Mode:
Circulator will vary speed to maintain desired feet
of head constant pressure curve. There are 5 setting
options: 6 - 30 feet.
Orange LED
C