Submittal Sheet

50 10 15 20 25 30 35 40 45 50 55
Flow Rate Q [GPM]
0
5
10
15
20
25
30
35
Head [ft.]
0034e High-Eciency Circulator
activeADAPT Range
Purple LED
activeADAPT
50 10 15 20 25 30 35 40 45 50 55
Flow Rate Q [GPM]
0
30
60
90
120
150
180
Power [W]
Power Consumption
0034e High-Eciency Circulator
activeADAPT Range
Purple LED
activeADAPT
activeADAPT™ Mode:
activeADAPT is an operating mode designed for constant
circulation systems. On this setting, the circulator will sense
changes in system ow and head conditions and adjust
the operating curve automatically.
50
0
5
10
15
20
25
30
35
10 15 20 25 30 35 40 45 50
Flow Rate Q [GPM]
Head [ft.]
MEDIUM
LOW
Head =13 ft.
Head = 26 ft.
0034e High-Eciency Circulator
Constant Pressure Curves
Orange LED
C
50
0
40
80
120
160
200
10 15 20 25 30 35 40 45 50
Flow Rate Q [GPM]
Power [W]
MEDIUM
LOW
Power Consumption
0034e High-Eciency Circulator
Constant Pressure Curves
Orange LED
C
Constant Pressure Mode:
At Low setting the circulator will vary speed to maintain
13 feet of head constant pressure. At Medium setting
the circulator will vary speed to maintain 26 feet of
head constant pressure.